Skip to main content
Schneider Electric A9N21022

Schneider Electric A9N21022 Prodis DT40 MCB, 4 A C-Curve 1P+

MPN A9N21022
Obsolete

Schneider Electric Prodis DT40, miniature circuit breaker, 4 A, C-curve, 1P+N, 4.5 kA Icn / 6 kA Icu, DIN rail clip-on, IP20.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9N21022 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage230 V AC 50 Hz between phase and neutral
Insulation voltage ui400 V AC 50 Hz
Breaking capacity4500 A Icn at 230 V AC 50 Hz conforming to EN/IEC 60898-1 6 kA Icu at 230...240 V AC 50 Hz conforming to IEC 60947-2
IP ratingIP20
Temp storage max70 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...70 °C

All specifications

A9N21022 additional specifications
ParameterValue
Pollution degree3 conforming to IEC 60947-2
ColorWhite
Depth78 mm
Width18 mm
Height81 mm
Electrical life cycles20000 cycles
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The Schneider Electric A9N21022 is a Prodis DT40 miniature circuit breaker rated 4 A with a C-curve trip characteristic (magnetic trip between 5 and 10 times In). The breaking capacity is 4.5 kA Icn at 230 V AC per EN/IEC 60898-1, and 6 kA Icu at 230–240 V AC per IEC 60947-2, so it covers both domestic-distribution and light-industrial panel applications.

The tunnel-type terminals accept 0.33–10 mm² flexible or 0.75–16 mm² rigid wire; strip length is 13 mm, tighten to 2 N·m. IP20 finger-safe terminals mean it's suited for enclosed distribution boards or control panels where incidental contact is prevented by the enclosure.

Rated for 50 Hz networks, pollution degree 3, overvoltage category IV, and tropicalised per IEC 60068-1 (class 2). Electrical and mechanical durability are both 20,000 cycles. The toggle gives local ON/OFF indication. Separate earth-leakage protection block can be added alongside.

MPN
A9N21022