Schneider Electric A9N21380

Schneider A9N21380 DT40N MCB, 40A D Curve 1P+N, 6kA/10kA

MPN A9N21380
Obsolete

Schneider Electric ProDis DT40N, A9N21380, miniature circuit breaker MCB, 1P+N, 40 A rated, D curve, 6 kA Icn / 10 kA Icu, clip-on DIN rail.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9N21380 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage230 V AC 50 Hz between phase and neutral
Insulation voltage ui400 V AC 50 Hz
IP ratingIP20
Temp storage max70 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...70 °C
Pollution degree3 conforming to IEC 60947-2

All specifications

A9N21380 additional specifications
ParameterValue
ColorWhite
Depth78 mm
Width18 mm
Height81 mm
Electrical life cycles10000 cycles
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The Schneider Electric A9N21380 is a ProDis DT40N miniature circuit breaker (MCB) sized for distribution boards. Rated 40 A with a D trip curve, it is built for loads with high inrush — motor starters, small transformers, or lighting ballasts — where the magnetic trip fires between 10 and 14 times the rated current (400 to 560 A instantaneously). The thermal-magnetic trip unit handles the overload side.

Breaking capacity and dual standard certification

This breaker carries dual certification to EN/IEC 60898-1 and EN/IEC 60947-2. Under the domestic-standard 60898-1, the rated breaking capacity (Icn) is 6000 A at 230 V AC. Under the industrial-standard 60947-2, the ultimate breaking capacity (Icu) is 10 kA at 230...240 V AC. That dual rating means the same unit can go into a residential DB (6 kA is enough for most domestic service entrances) or a light-industrial sub-distribution board where fault levels are higher. Overvoltage category IV and pollution degree 3 confirm it is rated for the mains entry point, not just downstream sub-circuits.

Termination and environment

The housing is IP20 finger-safe once installed. Limitation class 3 per 60898-1 limits let-through energy, which helps downstream selectivity with smaller MCBs.

MPN