Skip to main content
Schneider Electric A9N61654

A9N61654 C60PV-DC 2A MCB, Curve C, 800 V DC, 3 kA

MPN A9N61654
Obsolete

Schneider Electric C60PV-DC miniature circuit breaker, A9N61654, 2 A rated current, curve C, 2-pole, 800 V DC, 3 kA breaking capacity.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9N61654 key specifications
ParameterValue
Control typeToggle
Main product or component typeMiniature circuit-breaker
Voltage800 V DC
Insulation voltage ui1000 V DC
Breaking capacity3 kA Icu at 650 V DC 1.5 kA Icu at 800 V DC
Utilization categoryCategory A conforming to EN/IEC 60947-2
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degree2

All specifications

A9N61654 additional specifications
ParameterValue
ColorWhite
Depth77.4 mm
Width72 mm
Height132.7 mm
Electrical life cycles1500 cycles L/R = 2 ms
Mechanical life cycles20000 cycles
Operating temperature-25...70 °C

Product details

The Schneider Electric A9N61654 is a C60PV-DC miniature circuit breaker rated 2 A with a C tripping curve, 2-pole, designed for DC networks up to 800 V DC. It carries a breaking capacity of 3 kA Icu at 650 V DC and 1.5 kA Icu at 800 V DC, certified to EN/IEC 60947-2. The part is polarity-insensitive, meaning it can protect against bi-directional current — a key feature for PV strings where reverse current is possible.

The 3 kA / 1.5 kA breaking capacity at 650 V / 800 V DC tells you the maximum fault current it can safely interrupt — if your array's short-circuit current exceeds that, you need a higher-rated breaker upstream. The 1000 V DC insulation voltage (Ui) confirms the internal clearance is rated for the full system voltage.

This MCB is made for DC circuits in small commercial and residential solar PV arrays, battery banks, or DC distribution panels. The tunnel terminals accept 1...25 mm² rigid or 1...16 mm² flexible wire; strip length is 14 mm, torque to 2.5 N·m. The white housing and toggle control make it easy to identify and operate in a crowded panel.

MPN