Skip to main content
Schneider Electric A9Q22425

A9Q22425 Vigi iC60 4P 25A 100mA Type A RCD, Active

MPN A9Q22425
Active

Schneider Electric Acti9 Vigi iC60, add-on residual current device, 4P, 25 A, 100 mA, Type A, instantaneous, voltage independent, clip-on DIN rail.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9Q22425 specifications
ParameterValue
Main product or component typeAdd-on residual current device
Voltage230...415 V AC 50/60 Hz conforming to EN/IEC 61009-1 230...415 V AC 50/60 Hz conforming to EN/IEC 61009-2-1
Insulation voltage ui500 V AC 50/60 Hz conforming to IEC 60947-2
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degree3 conforming to IEC 60947-2
Depth73.5 mm
Width54 mm
Height91 mm
Operating temperature-25...60 °C

Product details

The A9Q22425 is an Acti9 Vigi iC60 add-on residual current device (RCD) — a 4-pole, 25 A, 100 mA, Type A block that plugs directly onto the outgoing side of a compatible iC60 MCB. The 54 mm width (6 x 9 mm pitches) and 73.5 mm depth fit the standard Acti9 modular grid, and the bottom tunnel terminals accept up to 25 mm² rigid cable.

The 100 mA sensitivity and Type A waveform detection cover sinusoidal AC and pulsating DC earth faults — the standard choice for final circuits with electronics, VFDs, or single-phase rectified loads. The instantaneous trip (no intentional delay) means it clears a fault in under 300 ms, which is the default for socket-outlet and general-purpose circuits where selectivity with an upstream time-delayed RCD is designed in, not assumed. The 25 A rated current matches a 25 A MCB partner; the plug-in mechanical and electrical connection to the MCB means the assembly occupies the same DIN pitch as the breaker alone, saving a module width over a standalone RCD. Pollution degree 3 per IEC 60947-2 means the device is rated for the conductive-dust and occasional-condensation environment of a typical industrial panel — not just clean residential switchgear. The 6 kV impulse withstand voltage (Uimp) and 500 V rated insulation voltage (Ui) give headroom for 230/400 V networks with transient surges. The IP20 (body) and IP40 (modular enclosure) ratings are normal for enclosed distribution boards; no special sealing is needed inside the cabinet.

The A9Q22425 carries an Active lifecycle status from Schneider Electric. No cross-reference or substitute is needed — the part is the standard fit.

MPN
A9Q22425