Skip to main content
Schneider Electric A9R04240

Schneider Electric A9R04240 Acti9 iID RCCB, 40 A, 300 mA, Ty

MPN A9R04240
Active

Schneider Electric Acti9 iID, residual current circuit breaker (RCCB), 2P, 40 A, 300 mA sensitivity, Type A, 220-240 V AC, clip-on DIN rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9R04240 specifications
ParameterValue
Control typeToggle
Voltage220...240 V AC 50/60 Hz
Insulation voltage ui500 V AC 50/60 Hz
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degree3
ColorWhite
Depth73.5 mm
Width36 mm
Height91 mm
Electrical life cyclesAC-1: 15000 cycles
Mechanical life cycles20000 cycles
Operating temperature-25...60 °C

Product details

It's a 2-pole unit rated 40 A continuous, with 300 mA sensitivity, Type A (pulsating DC and sinusoidal AC residual currents). The 220-240 V AC 50/60 Hz operational voltage covers standard single-phase supplies across most European and Asian distribution boards. Mounts via clip-on onto DIN rail — the 36 mm width (two modular pitches) fits standard enclosure cutouts. The white housing carries a toggle control and a contact-position indicator; a padlocking provision locks the toggle for lockout/tagout. Neutral is on the left, and the terminals accept up to 35 mm² rigid or 25 mm² flexible conductors, with a stripping length of 14 mm and tightening torque of 3.5 N·m.

It's not for personal shock protection — that demands 30 mA or lower. Type A detection covers the pulsed DC waveforms from single-phase rectifiers (common in washing machines, LED drivers, VFDs), so this RCCB is suited for mixed residential and light commercial loads. The 6 kV impulse withstand voltage (Uimp) means it survives transient surges from nearby lightning or switching without internal flashover. Electrical durability is 15,000 cycles under AC-1 (resistive load), mechanical durability 20,000 cycles. That's a solid service life for a distribution board that cycles a few times a year — not a daily-switched load, but it will outlast the building fit-out.

The 8/20 µs impulse withstand test at 250 A (per the same standard) confirms the device's immunity to surge currents without nuisance tripping. IP20 on the terminals, IP40 inside a modular enclosure — fine for dry indoor panels; not for washdown areas.

MPN
A9R04240