Skip to main content
Schneider Electric A9R11292

Schneider Electric A9R11292 Acti9 RCCB-ID, 125 A, 30 mA, 2P

MPN A9R11292
Active

Schneider Electric Acti9 RCCB-ID, residual current circuit breaker (RCCB), 2P, 125 A, 30 mA, Type AC, 230 V AC, 50 Hz, grey.

$801.11 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9R11292 specifications
ParameterValue
Control typeToggle
Voltage230 V AC 50 Hz conforming to IEC/EN 61008-1 230 V AC 50 Hz conforming to IEC/EN 61008-2-1
Insulation voltage ui400 V AC 50 Hz conforming to IEC/EN 61008-1 400 V AC 50 Hz conforming to IEC/EN 61008-2-1
Terminal pitch18 mm between phases
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max40 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degree3
ColorGrey
Depth76 mm
Width36 mm
Height86 mm
Electrical life cycles2000 cycles
Mechanical life cycles5000 cycles
Operating temperature-25...40 °C

Product details

What this RCCB is and what it guards

The Schneider Electric A9R11292 is a 2-pole residual current circuit breaker (RCCB) from the Acti9 range, rated 125 A at 230 V AC, 50 Hz, with 30 mA earth-leakage sensitivity and Type AC protection.

125 A rated current (In) and 230 V operational voltage (Ue) set the load envelope: this RCCB handles the full incoming feed for a sub-distribution board or a high-load outgoer, not just a final subcircuit. The 30 mA sensitivity (IΔn) is the standard for personal protection against indirect contact — it's fast enough to clear before heart fibrillation sets in. The breaking capacity Im is 1250 A at 230 V — that's the maximum prospective fault current the RCCB can interrupt without welding contacts, and it's well above typical domestic fault levels but below what you'd see on a heavy industrial bus.

Tunnel-type terminals accept 1.5–50 mm² rigid or 1.5–35 mm² flexible (single cable), or 1.5–16 mm² with two cables per pole. Tightening torque is 3 N·m; strip length 11 mm. IP20 on the body, IP40 inside a modular enclosure — fine for dry indoor distribution boards, not for washdown areas.

Certified to IEC/EN 61008-1 and IEC/EN 61008-2-1 (the RCCB product standards). Carries VDE quality label. Ambient storage range -40 to 85 °C.

MPN
A9R11292