Skip to main content
Schneider Electric A9Y84640

Schneider Electric A9Y84640 Vigi iC40 40A 30mA RCD, Type A-S

MPN A9Y84640
Active

Schneider Electric Acti9 Vigi iC40, add-on residual current device, 1P+N, 40 A rated current, 30 mA earth-leakage sensitivity, Type A-SI (Super Immunised), clip-on DIN rail mount.

$350.89 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9Y84640 specifications
ParameterValue
Main product or component typeAdd-on residual current device
Voltage230 V AC 50/60 Hz
Insulation voltage ui400 V AC 50/60 Hz conforming to EN/IEC 61009-2-1
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degree3 conforming to EN/IEC 61009-2-1
ColorWhite
Depth74 mm
Width36 mm
Height95 mm
Electrical life cycles10000 cycles
Mechanical life cycles20000 cycles
Operating temperature-25...60 °C

Product details

It provides earth-leakage protection for a single-phase circuit at 230 V AC, 50/60 Hz, with a rated current of 40 A and a 30 mA trip sensitivity. The 30 mA sensitivity covers standard personnel protection against direct contact, while the Type A-SI (Super Immunised) classification means it resists nuisance tripping from high-frequency leakage or pulsed DC waveforms — common on variable-speed drives, UPS systems, or LED lighting circuits that generate smooth DC fault currents a standard Type A might miss.

Tunnel terminals accept 1 to 16 mm² rigid or 1 to 10 mm² flexible cable, tightened to 2 N·m. At 74 mm deep and 95 mm tall, it fits standard modular enclosures with IP40 protection in the enclosure (IP20 on the terminals). The white housing matches the Acti9 family aesthetic for panel builders who care about visual consistency.

Electrical and environmental limits

Rated insulation voltage is 400 V AC, with an impulse withstand of 4 kV per EN/IEC 61009-2-1. Relative humidity tolerance is 95% at 55 °C. Maximum operating altitude is 2000 m.

MPN
A9Y84640