Skip to main content
Schneider Electric ATV1200A25156666

Schneider ATV1200A25156666 Altivar 1200 VFD, 2103 kW

MPN ATV1200A25156666
Active

Schneider Electric Altivar 1200 ATV1200A25156666 AC drive, 2103 kW motor power, 2970-3630 V supply, 36-pulse diode rectifier, floor-standing enclosure, CE marked.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATV1200A25156666 specifications
ParameterValue
Input type36 pulse diode rectifier bridge
Protection typeGround fault protection: drive
Coil voltage220 V
Current220 A
IP ratingIP41 / IP31 / IP42
Temp storage max60 °C
Temp storage min-10 °C
Temp operating max50 °C
Temp operating min0 °C
Storage temperature-10...60 °C
Pollution degreePollution degree 2
Depth1700 mm (high efficiency) 1700 mm (standard efficiency)
Width5170 mm (standard efficiency) 5470 mm (high efficiency)
Height2670 mm high efficiency 2670 mm standard efficiency
Operating positionVertical +/- 10 degree
Operating temperature0...40 °C 40...50 °C (with current derating of 2 % per °C)

Product details

2103 kW medium-voltage drive in a floor-standing cabinet

The Schneider Electric ATV1200A25156666 is a medium-voltage Altivar 1200 AC drive rated for 2103 kW motor power at a supply voltage of 2970-3630 V. It uses a 36-pulse diode rectifier bridge input, which inherently reduces line-side harmonics without an external filter. The drive ships in a floor-standing enclosure with separate air flows for the power section and control compartment. Dimensions are substantial: 2670 mm high, 5170 mm wide (standard efficiency) or 5470 mm wide (high efficiency), and 1700 mm deep. This is a current-production unit (lifecycle stage: current). It is sourced to order against your BOM quantity; availability and pricing are confirmed at RFQ time.

Overload profile and short-circuit withstand

The drive offers two overload profiles: standard overload handles 1.2× In for 60 s and 1.5× In for 3 s; high overload handles 1.5× In for 60 s and 1.85× In for 3 s. This lets you match the drive to either normal-duty or heavy-duty starting cycles. Prospective line short-circuit current is rated at 31.5 kA for 150 ms, giving the protection engineer a clear coordination target for upstream switchgear. Dielectric strength between earth and power terminals is tested at 20 kV AC, consistent with the medium-voltage isolation requirements of EN/IEC 61800-5-1.

Physical layout and site planning

The enclosure stands 2670 mm tall and requires a floor footprint of roughly 5.2 m × 1.7 m. Two width variants exist: 5170 mm for standard efficiency and 5470 mm for high efficiency — confirm which version your BOM specifies before allocating floor space. Cooling is forced convection with a volume of 23,100 m³/h (both efficiency variants) and an optional 43,200 m³/h fan. The noise level at full cooling is 80 dB — plan for hearing protection in the drive room. Operating altitude is 1000-2000 m with a current derating of 0.6 % per 100 m above 1000 m. The drive must be installed vertically within ±10 degrees.

The ATV1200A25156666 carries CE marking and complies with EN/IEC 60204-11, EN/IEC 60529, EN/IEC 61800-3 (EMC), EN/IEC 61800-4, and EN/IEC 61800-5-1 (safety). Pollution degree 2 per EN/IEC 61800-5-1 applies. The drive composition includes a phase-shifting transformer, 18 power cells, medium-voltage arrestors, cooling fans, and an HMI. Electrical isolation between power and control circuits is provided. I/O complement: 4 software-configurable analogue inputs (0-20 mA / 4-20 mA), 1 analogue output (same range), and 6 discrete inputs (expandable to 10). The control supply is 220 V AC, 3 kVA, with an optional 220 V AC/DC external supply.

MPN
ATV1200A25156666