Schneider Electric ATV1200A26001010 AC Drive, 2174 kW

MPN ATV1200A26001010
Active

Schneider Electric Altivar 1200 ATV1200A26001010 medium-voltage AC drive, 2174 kW motor power, 2600 kVA apparent power, 48-pulse diode rectifier input, 2970…3630 V supply, floor-standing enclosure.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATV1200A26001010 specifications
ParameterValue
Input type48 pulse diode rectifier bridge
Protection typeGround fault protection: drive
Coil voltage220 V
Current150 A
IP ratingIP42 / IP41 / IP31
Temp storage max60 °C
Temp storage min-10 °C
Temp operating max50 °C
Temp operating min0 °C
Storage temperature-10...60 °C
Pollution degreePollution degree 2
Depth1500 mm (standard efficiency)
Width6060 mm (standard efficiency)
Height2740 mm standard efficiency
Operating positionVertical +/- 10 degree
Operating temperature0...40 °C 40...50 °C (with current derating of 2 % per °C)

Product details

The ATV1200A26001010 is rated for 2174 kW motor output at the shaft, with an apparent power of 2600 kVA. That apparent power figure drives the upstream transformer and cable sizing — the feeder must support 2600 kVA continuous, not just the motor nameplate kW. Input supply voltage range is 2970…3630 V, placing this drive squarely in the medium-voltage class (typically 3.3 kV nominal grids). The 48-pulse diode rectifier bridge reduces line-side harmonics below IEEE 519 thresholds without external filters — a key advantage for sites with sensitive co-located equipment or utility harmonic limits. Overload capability is specified as 1.2 × In for 60 s (standard duty) and 1.5 × In for 3 s, with a high-overload profile reaching 1.85 × In for 3 s. This lets the drive handle motor starting inrush and short-duration load spikes without tripping, but the 60 s window at 1.2 × In is the practical limit for continuous overload coordination with the upstream breaker.

Floor-standing enclosure with separate air flows — physical integration constraints

The drive ships in a floor-standing enclosure measuring 1500 mm deep, 6060 mm wide, and 2740 mm high. That footprint demands a dedicated electrical room with a reinforced floor — the width alone exceeds a standard shipping container's internal width, so site access and rigging must be planned before delivery. Cooling is forced convection with separate air flows — the enclosure is designed to draw cooling air from the room and exhaust it separately, so the heat load (43,200 m³/h airflow,) must be factored into the room's HVAC capacity. Operating altitude derating starts at 1000 m, with 0.6 % current reduction per 100 m above that. The product composition includes a phase-shifting transformer, 24 power cells, medium-voltage arrestors, cooling fans, and a human-machine interface. The transformer is the heaviest single component — verify floor loading before positioning.

Compliance and lifecycle — current production, CE marked

Lifecycle status is listed as current production. The drive carries CE marking and complies with EN/IEC 60204-11, EN/IEC 60529, EN/IEC 61800-3, EN/IEC 61800-4, and EN/IEC 61800-5-1. These cover electrical safety, EMC, enclosure protection, and adjustable-speed drive performance standards. Dielectric strength is 28 kV AC between earth and power terminals, and the prospective line short-circuit current withstand is 31.5 kA for 150 ms. That SCCR rating means the drive can withstand a bolted fault on its input bus for up to 150 ms without catastrophic failure — coordination with the upstream breaker must clear the fault within that window.

MPN