Skip to main content
Schneider Electric ATV1200A44706060

Schneider Electric ATV1200A44706060 Altivar 1200, 3737 kW

MPN ATV1200A44706060
Active

Schneider Electric Altivar 1200 series, ATV1200A44706060, medium-voltage variable speed drive, 3737 kW motor power, 4470 kVA apparent power, 30-pulse diode rectifier input, floor-standing enclosure.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATV1200A44706060 specifications
ParameterValue
Input type30 pulse diode rectifier bridge
Protection typeGround fault protection: drive
Coil voltage220 V
Current490 A
IP ratingIP31 / IP41 / IP42
Temp storage max60 °C
Temp storage min-10 °C
Temp operating max50 °C
Temp operating min0 °C
Storage temperature-10...60 °C
Pollution degreePollution degree 2
Depth1700 mm (standard efficiency) 1800 mm (high efficiency)
Width6370 mm (high efficiency) 6070 mm (standard efficiency)
Height2740 mm standard efficiency 3040 mm high efficiency
Operating positionVertical +/- 10 degree
Operating temperature0...40 °C 40...50 °C (with current derating of 2 % per °C)

Product details

Medium-voltage drive for large synchronous and asynchronous motors

The Schneider Electric ATV1200A44706060 is a medium-voltage variable speed drive from the Altivar 1200 family, rated for 3737 kW motor power with 4470 kVA apparent power. It drives both synchronous and asynchronous motors, making it suitable for large pumps, compressors, conveyors, and fans in heavy industrial settings. The 30-pulse diode rectifier bridge input stage draws 490 A line current at supply voltage limits of 2970 to 3630 V, delivering a clean input waveform that meets EN/IEC 61800-3 EMC requirements without external filtering — the integrated EMC filter is standard.

Physical footprint and installation constraints

This drive ships as a floor-standing enclosure with separate air flows for power and control sections. Standard efficiency dimensions are 1700 mm deep, 6070 mm wide, 2740 mm high; the high-efficiency variant adds depth to 1800 mm, width to 6370 mm, and height to 3040 mm — verify floor space and overhead clearance before positioning. Operating position is vertical within ±10 degrees. Forced convection cooling moves 46500 m³/h of air through the cabinet; the noise level at full cooling is 80 dB — ear protection zones apply near the drive. Power connections use M10 bar-type terminals accepting 6 x 40 mm² cable per phase, entry from top or bottom. The phase-shifting transformer and 15 power cells are integrated inside the enclosure, along with medium-voltage arrestors and cooling fans.

Overload capability and motor protection

Overload withstand is configurable: standard overload handles 1.2× rated current for 60 seconds and 1.5× for 3 seconds; high overload mode handles 1.5× for 60 seconds and 1.85× for 3 seconds. This allows matching the drive to either constant-torque or variable-torque load profiles. Ground fault protection is built into the drive. Dielectric strength between earth and power terminals is 20 kV AC, with electrical isolation between power and control circuits. Pollution degree 2 per EN/IEC 61800-5-1 applies. Speed range is 20 to 100% of base speed. For operation above 1000 m altitude, derate current by 0.6% per 100 m up to 2000 m.

Control I/O and auxiliary supplies

The drive includes 4 software-configurable analogue inputs (0–20 mA / 4–20 mA, 24 V max, 250 Ω impedance) and 1 analogue output of the same type. Discrete inputs number 6 standard, expandable to 10 with the optional module. External control supply is 220 V AC at 3 kVA, with an optional 220 V AC/DC supply. The cooling fan runs on a separate 380 V AC supply — this keeps the control electronics powered independently from the fan circuit for safe commissioning and diagnostics.

Active production and sourcing posture

CE marking is applied. Standards compliance includes EN/IEC 60204-11, EN/IEC 60529, EN/IEC 61800-3, EN/IEC 61800-4, and EN/IEC 61800-5-1. Overvoltage category II per the drive standard.