Skip to main content
Schneider Electric ATV1200A60006363

Schneider ATV1200A60006363 Altivar 1200 MV Drive, 4473 kW

MPN ATV1200A60006363
Active

Schneider Electric Altivar 1200 ATV1200A60006363, medium-voltage AC drive, 4473 kW motor power, 2970–3630 V supply, 36-pulse diode rectifier, floor-standing enclosure.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATV1200A60006363 specifications
ParameterValue
Input type36 pulse diode rectifier bridge
Protection typeGround fault protection: drive
Coil voltage220 V
Current490 A
IP ratingIP31 / IP41 / IP42
Temp storage max60 °C
Temp storage min-10 °C
Temp operating max50 °C
Temp operating min0 °C
Storage temperature-10...60 °C
Pollution degreePollution degree 2
Depth1800 mm (standard efficiency) 1800 mm (high efficiency)
Width6670 mm (standard efficiency) 6970 mm (high efficiency)
Height2820 mm standard efficiency 3040 mm high efficiency
Operating positionVertical +/- 10 degree
Operating temperature0...40 °C 40...50 °C (with current derating of 2 % per °C)

Product details

What the 4473 kW rating and 36-pulse input mean for your installation

The ATV1200A60006363: This Altivar 1200 is a medium-voltage drive rated for 4473 kW motor power at a supply voltage of 2970 to 3630 V AC — it drives large induction motors in the 4–5 MW class, not the 480 V low-voltage world the category trail might suggest. The 36-pulse diode rectifier front end draws line current of 490 A and keeps input harmonics low enough that an external harmonic filter is typically unnecessary for IEEE 519 compliance — that is one less cabinet and one less SKU to spec. Apparent power is 5350 kVA, so the upstream transformer and switchgear must be sized for that full-load kVA plus the 1.2× overload for 60 seconds (standard duty) or 1.5× for 60 seconds (high overload profile).

Physical footprint — this is a walk-in cabinet, not a panel-mount drive

The ATV1200A60006363 ships as a floor-standing enclosure with separate air flows for the transformer and power cells. Standard-efficiency dimensions: 2820 mm high × 6670 mm wide × 1800 mm deep; the high-efficiency variant adds height (3040 mm) and width (6970 mm). Operating position is vertical ±10 degrees; altitude derating begins at 1000 m at 0.6 % per 100 m above that. Pollution degree 2 per EN/IEC 61800-5-1 means the enclosure location should be clean, non-conductive dust environment.

Standards, isolation, and protection — what the compliance marks cover

CE marked, with design compliance to EN/IEC 61800-3 (EMC), EN/IEC 61800-4 (harmonics), EN/IEC 61800-5-1 (safety), EN/IEC 60204-11 (machinery), and EN/IEC 60529 (enclosure protection). Electrical isolation between power and control circuits is standard. Dielectric strength is 20 kV AC between earth and power terminals — appropriate for the 3.3 kV class input voltage. Overvoltage category II per EN/IEC 61800-5-1. Ground fault protection is integral to the drive. Prospective line short-circuit current rating is 31.5 kA for 150 ms — coordinate upstream protection to clear within that window.

What is inside the cabinet — transformer, power cells, HMI

The drive comprises two plinths, a phase-shifting transformer, medium-voltage arrestors, cooling fans, a human-machine interface, and 18 power cells. The 36-pulse topology comes from the transformer's phase shift across the cells. Control supply is 220 V AC at 3 kVA external; cooling fan supply is 380 V AC internal. An optional external 220 V AC/DC control supply and external 380 V AC fan supply are available. I/O complement: 4 software-configurable analogue inputs (0–20 mA / 4–20 mA, 250 Ω impedance), 1 analogue output (same range), and 6 discrete inputs standard (10 optional).

MPN