Skip to main content
Schneider Electric ATV1200A62501010

Schneider ATV1200A62501010 AC Drive, 5225 kW, 6250 kVA

MPN ATV1200A62501010
Active

Schneider Electric Altivar 1200 ATV1200A62501010 medium-voltage AC drive, 5225 kW motor power, 6250 kVA apparent power, 48-pulse diode rectifier input, 2970-3630 V supply, floor-standing enclosure.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATV1200A62501010 specifications
ParameterValue
Input type48 pulse diode rectifier bridge
Protection typeGround fault protection: drive
Coil voltage220 V
Current410 A
IP ratingIP31 / IP42 / IP41
Temp storage max60 °C
Temp storage min-10 °C
Temp operating max50 °C
Temp operating min0 °C
Storage temperature-10...60 °C
Pollution degreePollution degree 2
Depth1600 mm (standard efficiency)
Width9070 mm (standard efficiency)
Height3040 mm standard efficiency
Operating positionVertical +/- 10 degree
Operating temperature0...40 °C 40...50 °C (with current derating of 2 % per °C)

Product details

5225 kW medium-voltage drive with 48-pulse input

The ATV1200A62501010 is a Schneider Electric Altivar 1200 medium-voltage AC drive rated for 5225 kW motor power with 6250 kVA apparent power, designed for large asynchronous motor loads in industrial applications. The 48-pulse diode rectifier bridge input stage provides inherent harmonic mitigation, reducing line-side distortion without external filters — a key advantage for installations with strict power quality requirements. Supply voltage range is 2970 to 3630 V AC, placing this drive firmly in the medium-voltage class for applications where step-down transformers are impractical or undesirable.

Overload capability and load profile matching

The drive offers two overload profiles: standard overload at 1.2× In for 60 s or 1.5× In for 3 s, and high overload at 1.5× In for 60 s or 1.85× In for 3 s. The high-overload curve suits variable-torque loads like conveyors or extruders that need short-duration torque bursts. Line current draw is 410 A at rated conditions; the prospective short-circuit current withstand is 31.5 kA for 150 ms, which sets the SCCR coordination requirement for upstream protection.

Physical footprint and cooling architecture

The drive ships in a floor-standing enclosure with separate air flows for power and control sections. Dimensions are 3040 mm high, 9070 mm wide, and 1600 mm deep — this is a large, dedicated drive room installation, not a panel-mount unit. Forced convection cooling moves 56,400 m³/h of air at standard efficiency. The audible noise level is 80 dB — hearing protection is required in the drive room during operation. Operating altitude derating applies above 1000 m: 0.6 % current derating per 100 m up to 2000 m. Ambient relative humidity range is 0 to 90 % (0 to 95 % optional).

Standards compliance and approvals

The drive carries CE marking and complies with EN/IEC 60204-11, EN/IEC 60529, EN/IEC 61800-3, EN/IEC 61800-4, and EN/IEC 61800-5-1. Pollution degree 2 per EN/IEC 61800-5-1 applies. Dielectric strength is 28 kV AC between earth and power terminals. Electrical isolation between power and control circuits is maintained per standard.

The product composition includes the plinth, phase-shifting transformer, medium-voltage arrestors, cooling fans, HMI, and 24 power cells. This is a complete drive system, not a bare chassis — the transformer and cell architecture are integral to the 48-pulse design.

MPN