Schneider ATV212HD18N4LCD AC Drive, 18.5 kW / 25 hp, 480 V

MPN ATV212HD18N4LCD
Obsolete

Schneider Electric Altivar 212 series, ATV212HD18N4LCD AC drive, 18.5 kW / 25 hp, 480 V, 27.8 A line current, integrated C2 EMC filter, IP20, 245 x 330 x 190 mm.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATV212HD18N4LCD specifications
ParameterValue
Connector type1 RJ45 1 open style
Main product or component typeVariable speed drive
Voltage= 1 mOhm 500 V DC for 1 minute
Current27.8 A at 480 V 34.8 A at 380 V
Horsepower25 hp
Frequency50...60 Hz - 5...5 %
Temp storage max70 °C
Temp storage min-25 °C
Temp operating max50 °C
Temp operating min-10 °C
Storage temperature-25...70 °C
Pollution degree2 conforming to IEC 61800-5-1
Depth190 mm
Width245 mm
Height330 mm
Data format8 bits, 1 stop, odd even or no configurable parity
Operating positionVertical +/- 10 degree

Product details

18.5 kW at 480 V — motor power and line-side draw

The ATV212HD18N4LCD: This Altivar 212 drive is rated for 18.5 kW (25 hp) output to an asynchronous motor at 480 V supply. Line current at that voltage is 27.8 A; at 380 V it draws 34.8 A. That 27.8 A figure governs the upstream breaker and cable sizing — the drive itself handles the lower-voltage current rise without derating the output stage.

Integrated C2 EMC filter — no external box needed

The ATV212HD18N4LCD ships with a Class C2 EMC filter built in. For a panel builder, that means the drive meets conducted emission limits for industrial environments (second environment / C2 per IEC 61800-3) without an add-on filter module. The standards list covers both C1 and C2 in environments 1 and 2, plus UL Type 1 — so it qualifies for North American and European installs with the same hardware.

Protection suite — 12 monitored faults

The drive monitors overcurrent, short-circuit between motor phases, earth faults on the output, DC bus overvoltage and undervoltage, input phase loss, motor thermal overload, PTC probe input, and control circuit break. That covers the commissioning checklist for most pump, fan, and conveyor starts — no external motor relay needed for the thermal protection leg.

Modbus RTU on RS-485 — standard comms, no option card

The drive has a 2-wire RS-485 physical interface with Modbus RTU protocol, configurable 9600 or 19200 bps, 8 data bits, 1 stop, parity configurable. Addressing range is 1–247. For a controls integrator wiring a multi-drive line, this is the native fieldbus — no extra communication card required for Modbus. An optional LonWorks card is listed for building automation tie-in.