Schneider Electric ATV6000C240A4242ND

Schneider ATV6000C240A4242ND AC Drive, 1920 kW, 2400 kVA

MPN ATV6000C240A4242ND
Active

Schneider Electric Altivar Process ATV6000, ATV6000C240A4242ND AC Drive (VFD) 480V, 1920 kW normal duty / 1540 kW heavy duty, 2400 kVA, 24-pulse diode rectifier, floor-standing enclosure.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATV6000C240A4242ND specifications
ParameterValue
Input type24 pulse diode rectifier bridge
Display type10 inch LCD touch screen multi-language
Connector type2 RJ45 on the control block)Ethernet IP/Modbus TCP 1 RJ45 on the control block)Modbus serial
Current333 A normal duty 267 A heavy duty
Frequency50 Hz +/- 5 %
Phases3-phase
IP ratingIP31
Temp storage max50 °C
Temp storage min0 °C
Temp operating max60 °C
Temp operating min1.2 °C
Storage temperature32...122 °F (0...50 °C)
Pollution degreePollution degree 2
Depth59.06 in (1500.0 mm)
Width199.2 in (5060.0 mm)
Height108.3 in (2751.0 mm)
Operating temperature32...104 °F (0...40 °C) 104...122 °F (40...50 °C) with derating factor -13...158 °F (-25...70 °C) during transport

Product details

Motor power and line current — normal vs heavy duty

The ATV6000C240A4242ND: Rated 1920 kW normal duty and 1540 kW heavy duty, with line current 333 A normal / 267 A heavy duty. The heavy-duty figure governs continuous overload capability for high-torque loads like crushers or mills; the normal-duty rating applies when the load profile stays below the motor's service factor.

24-pulse rectifier — THDI <3% without external filtering

The 24-pulse diode rectifier front end keeps total harmonic current distortion below 3% per IEEE 519-1992, so the drive meets utility power-quality limits without adding a separate harmonic filter. Power factor is 96%, which reduces the kVA draw from the upstream transformer.

Regulatory acceptance — cULus, CE, UKCA

Marked cULus, CE, and UKCA, with standards compliance to IEC 61800-3/-4/-5-1, IEC 60529, IEEE 519, and UL 347A. That covers North American and EU installation without a separate certification step — a practical advantage for a multinational project spec.

Floor-standing enclosure — plan the substation footprint

The drive ships in a floor-standing enclosure measuring 59.06 in deep, 199.2 in wide, and 108.3 in high. That footprint dictates the MCC room or substation layout — allow front and rear access clearance per the installation manual for cable entry and cooling airflow.

MPN
ATV6000C240A4242ND