Schneider Electric ATV650D15N4E

Schneider ATV650D15N4E Altivar Process VFD, 20 HP, IP55

MPN ATV650D15N4E
Active

Schneider Electric Altivar Process ATV600 series, ATV650D15N4E variable speed drive, 20 HP / 15 kW normal duty, 15 HP / 11 kW heavy duty, 380-480 V, IP55, with integrated disconnect switch.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATV650D15N4E specifications
ParameterValue
Main product or component typeVariable speed drive
Current23.3 A at 480 V (normal duty) 20.6 A at 380 V (heavy duty) 18.1 A at 480 V (heavy duty) 27 A at 380 V (normal duty)
Horsepower15 hp heavy duty 20 hp normal duty
Frequency50...60 Hz - 5...5 %
IP ratingIP55
Temp storage max70 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-40 °C
Storage temperature-40...70 °C
Pollution degree3
Operating positionVertical +/- 10 degree
Operating temperature40...50 °C (with derating factor) -15...40 °C (without derating)

Product details

Built-in disconnect switch and IP55 enclosure

The ATV650D15N4E: This ATV650 variant ships with an integrated disconnect switch, so the drive can be isolated locally for maintenance without an external disconnect upstream — a clean panel layout for a single-drive machine. No separate cabinet required.

31.7 A continuous output at 4 kHz — normal vs heavy duty

Rated 31.7 A continuous at 4 kHz carrier for normal duty (20 HP / 15 kW), and 23.5 A at 4 kHz for heavy duty (15 HP / 11 kW). The heavy-duty rating gives headroom for constant-torque loads like conveyors or extruders; normal duty suits variable-torque pumps and fans. Line current draw is 23.3 A at 480 V normal duty, 27 A at 380 V normal duty — size the branch circuit protection and input cable accordingly. The drive includes an integrated EMC filter: compliant with Category C2 at 50 m cable length, and Category C3 at 150 m.

STO SIL 3 and multi-protocol option slots

The STO function is the primary means for safe maintenance access on the driven load. Slot A accepts fieldbus option cards: PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, CANopen, Profibus DP V1, Ethernet Powerlink, or BACnet MS/TP. Slot A and slot B also accept digital/analog I/O extension or relay output cards. The drive ships with Modbus serial and Modbus TCP on the base board.

Wall-mount integration — cooling and derating

Wall-mount only (vertical ±10°), forced-convection cooled. At altitudes above 1000 m, derate 1 % per 100 m up to 4800 m. Pollution degree 3 environment — the drive is rated for industrial atmospheres with conductive dust or humidity. Overvoltage category III means it can be connected directly to the building distribution panel without additional surge suppression on the input.

Current production lifecycle stage — this ATV650 variant is an active catalog item from Schneider Electric.