Skip to main content
Schneider Electric ATV9A0C31Q6

ATV9A0C31Q6 Altivar Process ATV900 Drive, 315 kW

MPN ATV9A0C31Q6
Active

Schneider Electric Altivar Process ATV900 series, ATV9A0C31Q6 modular variable speed drive, 315 kW at 600 V normal duty, integrated EMC filter C3, STO SIL3.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATV9A0C31Q6 specifications
ParameterValue
Main product or component typeVariable speed drive
Current316.0 A 600 V normal duty) 255.0 A 600 V heavy duty)
Frequency50...60 Hz +/- 5 %
Temp storage max70 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min1.2 °C
Storage temperature-40...158 °F (-40...70 °C)
Pollution degreePollution degree 2

Product details

The ATV9A0C31Q6 is the 315 kW normal-duty (250 kW heavy-duty) member of the Altivar Process ATV900 family, sized for a 600 V supply line. This modular version ships as a kit: control unit, power module, mounting kit, and a fuse set. The drive handles synchronous and asynchronous motors, with a switching frequency adjustable from 2 to 4.9 kHz – expect derating if you push above the default.

The line current at 600 V normal duty hits 316 A; heavy duty pulls 255 A. That's the number your upstream breaker and cable need to handle – not the motor FLA. Prospective line Isc is rated for 50 kA, so if your panel SCCR is below that, you may need a current-limiting fuse upstream. The integrated EMC filter is rated for 300 m of motor cable and meets IEC 61800-3 category C3. That's a second-environment (industrial) filter – it will pass conducted emissions for a typical plant floor but don't count on it for a residential or first-environment install without external filtering. Keep the motor cable shield bonded at both ends; the filter expects a low-impedance ground path. Safe Torque Off (STO) is SIL 3 capable. The drive provides its own 24 V DC supply for the STO and digital inputs (21-27 V). If you're wiring a safety relay or PLC safety output, remember this supply is referenced to the control common – isolate if your safety circuit floats.

Signal integrity and control wiring

The control terminals are removable screw clamps accepting 0.5 to 1.5 mm² (AWG 20 to 16). The digital input supply is 24 V DC with a range of 19 to 30 V – that's wider than many PLC outputs, so a sagging 24 V rail won't drop the drive off. But if the digital inputs share the same supply as a noisy solenoid bank, you'll see phantom triggers; run a separate pair or add a filter. Modbus serial runs over a 2-wire RS-485 at 4.8, 9.6, 19.2, or 38.4 kbit/s, RTU frame, 1-247 addresses. The RJ45 port on slot A can take a Profibus, PROFINET, DeviceNet, EtherCAT, or CANopen card. For Modbus TCP, the native Ethernet port handles 10/100 Mbit/s, half/full duplex, auto-negotiation. If the line is daisy-chained, watch the cable length – the integrated EMC filter is for the motor cable, not the network.

Cabinet mount, IP00 chassis – rated for IP21 or IP54 after cabinet integration. Forced convection cooling; operating altitude 0-2000 m with derating above 1000 m. Environmental: 5-95% RH non-condensing, vibration resistance 0.5 gn at 13-200 Hz. The drive is IEC 61800-5-1 rated for pollution degree 2. That means non-conductive dust is acceptable, but if you're in a conductive dust or washdown area, you'll need an enclosure upgrade.

Sourcing and compliance reality

Supply is quoted to order. For a drive this size, expect a lead time that matches the power module assembly – typically a few weeks from RFQ, not off-the-shelf. No direct drop-in substitute within the same frame; the ATV900 family is segmented by power and cooling, so the 315 kW normal-duty unit is what you specify.

MPN
ATV9A0C31Q6