Skip to main content
Schneider Electric C10B42D040

C10B42D040 ComPacT NSX 40A 4P MCCB, 40 kA Icu at 240 V

MPN C10B42D040
Active

Schneider Electric ComPacT NSX, NSX100B frame, 40 A, 4P, MicroLogic 2.2 electronic trip unit, 40 kA Icu at 240 V AC, toggle control.

$393.00 – $645.73 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C10B42D040 key specifications
ParameterValue
Control typeToggle
Trip unit typeElectronic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C
Temp operating max70 °C

All specifications

C10B42D040 additional specifications
ParameterValue
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth86 mm
Width140 mm
Height161 mm
Electrical life cycles50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical life cycles50000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The C10B42D040 is a Schneider Electric ComPacT NSX molded-case circuit breaker in the NSX100B frame, rated 40 A at 40 °C with a MicroLogic 2.2 electronic trip unit. Four poles, toggle control, front-connected — it's built for distribution duty in a backplate-mounted panel.

This breaker delivers 40 kA Icu at 220/240 V AC, 25 kA at 380/415 V, 20 kA at 440 V, and 15 kA at 500 V — all per IEC 60947-2. For a 400 V distribution board, that 25 kA Icu gives you headroom above typical utility fault levels (often 18–22 kA), so you can coordinate downstream without cascading failures. The electronic trip also means you get adjustable long-time and short-time pickup — not just a thermal-magnetic fixed curve.

Connection pitch is 35 mm, and both line and load connections are front-accessed, so you can land cables without pulling the breaker out of the panel. IP40 enclosure protection keeps dust out but isn't rated for washdown — keep it inside a cabinet.

MPN