Skip to main content
Schneider Electric C10H34V040

C10H34V040 ComPacT NSX 40A Earth Leakage Circuit Breaker, 10

MPN C10H34V040
Active

Schneider Electric ComPacT NSX, earth leakage circuit breaker, 3P, 40 A, MicroLogic 4.2 electronic trip unit, 100 kA Icu at 240 V AC, EN/IEC 60947-2.

$1,063.78 – $2,067.12 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C10H34V040 key specifications
ParameterValue
Control typeToggle
Trip unit typeElectronic
Main product or component typeEarth leakage circuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui500 V AC 50/60 Hz
Breaking capacity100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 65 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C

All specifications

C10H34V040 additional specifications
ParameterValue
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth86 mm
Width105 mm
Height161 mm
Electrical life cycles50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical life cycles50000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The C10H34V040 is a Schneider Electric ComPacT NSX earth leakage circuit breaker, 3-pole, rated 40 A at 40 °C with a MicroLogic 4.2 electronic trip unit. It's built for distribution panels — backplate-mounted, front-connected, toggle-operated. The 100 kA Icu at 240 V AC (EN/IEC 60947-2) means it can safely interrupt a fault up to that level without upstream cascading; at 415 V AC it still holds 70 kA Icu. That's a high-interrupting-capacity frame (NSX100H) for high-fault locations like main switchboards or industrial sub-distribution.

Protection logic and trip unit

The earth-leakage is integrated, no add-on module.

Mechanical and electrical durability

Rated for 50,000 mechanical cycles and 50,000 electrical cycles at 440 V In (30,000 at 440 V In, 20,000 at 690 V In/2, 10,000 at 690 V In). That's a solid duty cycle for a distribution breaker — not a motor-starting device (Category A utilization), but fine for switching loads within its rated current. IK07 impact resistance handles accidental tool drops.

Current-production part (lifecycle stage: current). No LTB or EOL notice on record.

MPN
C10H34V040