Schneider Electric C10H3MA050

Schneider C10H3MA050 ComPacT NSX 3P 50A Magnetic Circuit Bre

MPN C10H3MA050
Active

Schneider Electric, ComPacT NSX, circuit breaker, C10H3MA050, 3P, 50 A, magnetic trip unit MA, 70 kA at 415 V AC.

$340.07 – $552.58 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C10H3MA050 key specifications
ParameterValue
Control typeToggle
Trip unit typeMagnetic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz
Breaking capacity100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 65 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C

All specifications

C10H3MA050 additional specifications
ParameterValue
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth86 mm
Width105 mm
Height161 mm
Electrical life cycles50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical life cycles50000 cycles
ApplicationMotor protection
Operating temperature-25...70 °C

Product details

The MA trip unit provides short-circuit (magnetic) protection only; there is no thermal overload element, so upstream or separate overload relay handles that function.

Rated Icu at 380/415 V AC is 70 kA, dropping to 65 kA at 440 V, 50 kA at 500 V, and 35 kA at 525 V. At 660/690 V AC it still holds 10 kA. Under UL 60947-4-1, Icu is 85 kA at 240 V AC and 65 kA at 480 V AC.

Front connections top and bottom. Connection pitch is 35 mm. IP40 protection, IK07 impact resistance. Ambient conditions: 0 to 95 % relative humidity, operating altitude up to 2000 m without derating, 2000–5000 m with derating.