Skip to main content
Schneider Electric C10N3MA003

Schneider Electric C10N3MA003 ComPacT NSX Circuit Breaker, 2

MPN C10N3MA003
Active

Schneider Electric ComPacT NSX circuit breaker, C10N3MA003, 3-pole, 2.5 A magnetic trip unit (MA), 50 kA breaking capacity at 415 V AC, motor protection application.

$321.02 – $502.25 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C10N3MA003 key specifications
ParameterValue
Control typeToggle
Trip unit typeMagnetic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C
Temp operating max70 °C

All specifications

C10N3MA003 additional specifications
ParameterValue
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth86 mm
Width105 mm
Height161 mm
Electrical life cycles50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical life cycles50000 cycles
ApplicationMotor protection
Operating temperature-25...70 °C

Product details

It provides short-circuit protection (magnetic) only, with no thermal overload element — that function is handled by a separate motor starter or overload relay upstream. The 3-pole breaker is rated for 50 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2, and carries a 90 kA Icu at 220/240 V AC. The MA trip unit is set at 2.5 A at 65 °C, meaning it will trip magnetically on short-circuit currents above that threshold, but does not track thermal heating in the motor circuit.

Motor protection — why the MA trip unit matters

This breaker is built for motor protection duty (Category A, per IEC 60947-2). The magnetic-only trip unit (MA) is standard for motor branch circuits where a separate overload relay handles thermal protection. The 2.5 A rating at 65 °C means it's sized for a small motor load — roughly 1.1 kW at 400 V three-phase, depending on motor full-load amps. The 3D protected poles configuration covers all three phases.

IP40 enclosure protection (finger-safe), IK07 impact resistance.

MPN
C10N3MA003