Skip to main content
Schneider Electric C10N42D040

Schneider Electric C10N42D040 ComPacT NSX 40A 4P MCCB, 50kA

MPN C10N42D040
Active

Schneider Electric ComPacT NSX, C10N42D040, 4P 40 A MCCB, MicroLogic 2.2 electronic trip unit, 50 kA at 415 V AC, toggle control.

$369.02 – $1,076.17 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C10N42D040 key specifications
ParameterValue
Control typeToggle
Trip unit typeElectronic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C
Temp operating max70 °C

All specifications

C10N42D040 additional specifications
ParameterValue
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth86 mm
Width140 mm
Height161 mm
Electrical life cycles50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical life cycles50000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The Schneider Electric C10N42D040 is a 4-pole ComPacT NSX100N molded-case circuit breaker rated 40 A at 40 °C, fitted with an electronic MicroLogic 2.2 trip unit. The toggle control and backplate mounting suit standard panel layouts.

At 40 A continuous and 50 kA Icu at 415 V AC, this breaker handles typical 40 A feeder or motor circuits in a 400 V distribution system without needing an upstream current-limiting fuse. The electronic trip unit (MicroLogic 2.2) provides adjustable long-time pickup and delay, plus fixed short-time and instantaneous settings — useful for coordinating with downstream branch breakers in a selective-coordination study. The 4-pole (4P) configuration with neutral on the left covers three-phase plus neutral systems common in European and Asian panel designs.

Backplate mounting with front-connect terminals (both upside and downside). IP40 front face and IK07 impact rating suit enclosed panel installation — not for washdown zones. The 5 accessory slots allow field-installable aux contacts, shunt trips, or under-voltage releases without removing the breaker from the panel.

MPN
C10N42D040