Skip to main content
Schneider Electric C10V3MA013

Schneider C10V3MA013 ComPacT NSX Circuit Breaker, 12.5 A, 85

MPN C10V3MA013
Active

Schneider Electric ComPacT NSX, C10V3MA013, 3-pole circuit breaker, magnetic-only MA trip unit rated 12.5 A at 65 °C, 85 kA Icu at 500 V AC.

$6.63 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C10V3MA013 key specifications
ParameterValue
Control typeToggle
Trip unit typeMagnetic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C
Temp operating max70 °C

All specifications

C10V3MA013 additional specifications
ParameterValue
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth86 mm
Width105 mm
Height161 mm
Electrical life cycles20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical life cycles20000 cycles
ApplicationMotor protection
Operating temperature-25...70 °C

Product details

Motor protection breaker with magnetic-only trip

Rated 12.5 A at 65 °C, it pairs with an external overload relay for full motor branch protection.

You size the breaker to the motor's full-load amps and let the external overload relay handle running protection. The magnetic trip unit provides instantaneous short-circuit protection only, with a fixed pickup typically around 12–14× In for MA trip curves. Breaking capacity of 85 kA Icu at 500 V AC and 75 kA at 690 V AC covers most industrial motor branch circuits; the HB1 code indicates the high-breaking version. The 3-pole design with front connections mounts flat on a backplate in either horizontal or vertical orientation.

Integration notes

The 35 mm connection pitch matches standard busbar systems. IP40 front protection and IK07 impact resistance are adequate for enclosed panel mounting — no washdown rating, so keep it inside the cabinet. Electrical durability is 20,000 cycles at 440 V In/2 and 10,000 cycles at 440 V In; mechanical durability is 20,000 cycles.

MPN
C10V3MA013