Schneider Electric C11F34V100B

Schneider C11F34V100B ComPacT NSXm MCCB, 100A, 36kA, 3P

MPN C11F34V100B
Active

Schneider Electric ComPacT NSXm, C11F34V100B, 100 A MCCB with MicroLogic 4.1 electronic trip unit, 36 kA at 415 V AC, 3P, integrated earth-leakage protection, grey (RAL 7016).

$1,448.82 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C11F34V100B key specifications
ParameterValue
Control typeToggle
Trip unit typeElectronic
Main product or component typeEarth leakage circuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui500 V AC 50/60 Hz
IP ratingIP40
Terminal pitch35 mm with spreaders 27 mm without spreaders
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C

All specifications

C11F34V100B additional specifications
ParameterValue
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degreeclass 3
ColorGrey (RAL 7016)
Depth80 mm
Width108 mm
Height144 mm
Electrical life cycles20000 cycles at 440 V In/2 10000 cycles at 440 V In
Mechanical life cycles20000 cycles
ApplicationDistribution
Safety categoryF 36 kA 415 V AC
Operating temperature-25...70 °C

Product details

What this 100 A MCCB does on the line

The Schneider Electric C11F34V100B is a ComPacT NSXm moulded-case circuit breaker rated 100 A at 40 °C, with a 36 kA interrupting capacity at 415 V AC — that F performance level means it clears faults up to that current without the arc re-striking, which is what keeps downstream gear from cooking on a bolted fault. Integrated earth-leakage protection is built in, with selectable sensitivity from 30 mA up to 5 A for both class A and class AC residual currents — that saves an external RCCB and a module of DIN rail space in a distribution board.

Panel fit and mounting reality

Three-pole (3P) design, 144 mm high by 108 mm wide by 80 mm deep, mounts on a backplate — not a DIN rail, so plan for a drilled mounting plate or an enclosure backpan. The 9-module pitch (9 x 9 mm = 81 mm wide footprint) matches standard modular enclosure cutouts. Connection pitch is 35 mm with spreaders, 27 mm without — that matters when you're laying out busbar runs or ordering pre-drilled lugs.

Lifecycle and compliance posture

Operating altitude is 2000 m without derating, 5000 m with derating; relative humidity 0–95 %. Electrical durability is 20,000 cycles at 440 V at rated current (In/2) and 10,000 cycles at full In — that's typical for a distribution breaker; not a switching device for frequent motor starts, but fine for infrequent manual isolation or backup protection.

MPN