Schneider Electric ComPacT NSXm 160NA, C124160BS, 4-pole switch disconnector, 160 A thermal current (Ith), AC-22/AC-23 rated, toggle control, fixed mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C124160BS key specifications
ParameterValue
Control typeToggle
Main product or component typeSwitch disconnector
Voltage440 V AC 50/60 Hz
Insulation voltage ui800 V
CurrentAC-23: 100 A AC 50/60 Hz AC-22: 160 A AC 50/60 Hz
Utilization categoryAC-22 A AC-23 A
IP ratingIP40
Terminal pitch27 mm
Temp storage max85 °C
Temp storage min-50 °C
Temp operating max70 °C
Temp operating min-25 °C

All specifications

C124160BS additional specifications
ParameterValue
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth80 mm
Width108 mm
Height137 mm
Electrical life cyclesAC-22 A: 20000 cycles 440 V AC 50/60 Hz Ie/2 AC-23 A: 20000 cycles 440 V AC 50/60 Hz Ie/2 AC-22 A: 10000 cycles 440 V AC 50/60 Hz Ie AC-23 A: 10000 cycles 440 V AC 50/60 Hz Ie
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

For motor switching (AC-23 duty), the rated operational current drops to 100 A at 440 V AC — the AC-23 category covers switching of motors and other highly inductive loads, so if this part is feeding a motor starter, the 100 A figure governs, not the 160 A thermal rating. For mixed resistive-inductive loads (AC-22), it carries the full 160 A. The short-circuit making capacity (Icm) is 2.13 kA for the switch-disconnector alone, but rises to 150 kA when installed with an upstream circuit breaker — that coordination is critical for panel selectivity studies. The rated short-time withstand current (Icw) is 1500 A for 1 s or 3 s, and 335 A for 20 s, which defines how long the device can carry fault current while the upstream protection clears.

The fixed-mount form factor and 108 mm width mean it occupies four standard 27 mm pole pitches. Terminals accept crimp lugs from 2.5 to 120 mm² for rigid or stranded aluminium/copper, or 2.5 to 95 mm² for flexible aluminium/copper bars — sized for the 160 A continuous rating. IP40 enclosure protection and IK07 impact resistance suit it for general-purpose panel installation where no washdown or dust ingress is expected.