Skip to main content
Schneider Electric C12H34V160B

Schneider Electric C12H34V160B ComPacT NSXm 160H, 160 A, 70

MPN C12H34V160B
Obsolete

Schneider Electric ComPacT NSXm 160H, 160 A, 70 kA at 415 V AC, 3P, MicroLogic 4.1 electronic trip unit with integrated earth-leakage, grey (RAL 7016).

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C12H34V160B key specifications
ParameterValue
Control typeToggle
Trip unit typeElectronic
Main product or component typeEarth leakage circuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui500 V AC 50/60 Hz
IP ratingIP40
Terminal pitch35 mm with spreaders 27 mm without spreaders
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C

All specifications

C12H34V160B additional specifications
ParameterValue
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degreeclass 3
ColorGrey (RAL 7016)
Depth80 mm
Width108 mm
Height144 mm
Electrical life cycles20000 cycles at 440 V In/2 10000 cycles at 440 V In
Mechanical life cycles20000 cycles
ApplicationDistribution
Safety categoryH 70 kA 415 V AC
Operating temperature-25...70 °C

Product details

ComPacT NSXm 160H — 160 A MCCB with integrated earth-leakage

The C12H34V160B is a Schneider Electric ComPacT NSXm 160H moulded-case circuit breaker (MCCB) rated 160 A at 40 °C, with a 70 kA interrupting capacity at 415 V AC — the H performance level. It carries a MicroLogic 4.1 electronic trip unit and integrated earth-leakage protection, making it a single-device solution for distribution circuits that need both overcurrent and ground-fault protection in one DIN-rail-mountable package.

The electronic trip unit (MicroLogic 4.1) provides adjustable long-time, short-time, and instantaneous protection curves, plus the integrated earth-leakage function with selectable sensitivity from 30 mA up to 5 A for both class A and class AC detection. That covers everything from personnel protection (30 mA) to equipment ground-fault (5 A) without a separate relay. The IP40 enclosure and IK07 impact rating handle typical panel conditions; not washdown-rated, so keep it inside the enclosure.

It occupies 9 module pitches (9 x 18 mm) on a DIN rail, 108 mm wide. Connection is front-facing for both line and load sides, using compression lugs or busbars. The connection pitch is 35 mm with spreaders, 27 mm without. The grey (RAL 7016) housing is standard for the ComPacT range. A green flag signals presence of auxiliary contacts.

MPN