Skip to main content
Schneider Electric C160N360FM

C160N360FM ComPacT NS 1600A, 50kA 415V AC, MicroLogic 6.0

MPN C160N360FM
Active

Schneider Electric ComPacT NS new generation, C160N360FM, 3P 1600A, 50 kA Icu at 415 V AC, MicroLogic 6.0 LSI electronic trip unit, fixed mount, manually operated.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C160N360FM key specifications
ParameterValue
Control typeManually operated
Trip unit typeElectronic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz conforming to IEC 60947-2
Poles3P
Utilization categoryCategory B
IP ratingIP40
Terminal pitch70 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C

All specifications

C160N360FM additional specifications
ParameterValue
Temp storage min-50 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degree3 conforming to IEC 60947
Depth147 mm
Width210 mm
Height327 mm
Electrical life cycles1000 cycles at 690 V In 2000 cycles at 690 V In/2 2000 cycles at 440 V In 5000 cycles at 440 V In/2
Mechanical life cycles10000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The C160N360FM is a Schneider Electric ComPacT NS new generation 3-pole circuit breaker rated 1600 A at 50 °C with a MicroLogic 6.0 electronic trip unit providing LSI protection (long-time, short-time, instantaneous). Its 85 kA Icu at 240 V AC and 50 kA Icu at 415 V AC per IEC 60947-2 mean it can safely interrupt fault currents up to those levels without upstream damage — critical for main or feeder breakers in distribution panels where high available fault current is expected. The breaker is manually operated, fixed-mounted to a backplate, and sized at 210 mm wide × 327 mm high × 147 mm deep — a footprint that fits standard switchboard compartments. Power losses are 74 W at rated current — a figure to budget for in enclosure thermal calculations, especially when multiple breakers are ganged. The IP40 front face and IK07 impact resistance suit indoor distribution boards; pollution degree 3 per IEC 60947 means it tolerates conductive pollution in industrial environments.

Protection & Selectivity

The MicroLogic 6.0 trip unit covers overload (L), short-time short-circuit (S), and instantaneous (I) protection. The electronic design allows adjustable pickup and time-delay settings on the L and S curves, enabling selective coordination with downstream breakers — a key requirement for service continuity in a distribution hierarchy. Thermal memory of 20 minutes prevents nuisance tripping on reclose after a mild overload.

Mechanical & Electrical Endurance

Mechanical durability is 10,000 cycles; electrical durability varies with load: 1,000 cycles at 690 V In, 2,000 cycles at 690 V In/2, 2,000 cycles at 440 V In, and 5,000 cycles at 440 V In/2. These figures guide maintenance scheduling for high-cycling applications like motor control centers or capacitor bank switching.

Environmental & Mounting

Operating altitude is 0 to 2000 m without derating, 2000 m to 5000 m with derating. Relative humidity range 0 to 95 %. Connection pitch is 70 mm between phase centers — standard for this frame size and compatible with common busbar systems.

MPN