Skip to main content
Schneider Electric C16B3

Schneider Electric C16B3 ComPacT NSX160B, 160A, 3P, 25kA/415

MPN C16B3
Active

Schneider Electric ComPacT NSX series, NSX160B basic frame, 160 A frame rating, 3 poles, 25 kA Icu at 415 V AC, without trip unit.

$145.83 – $216.63 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C16B3 key specifications
ParameterValue
Control typeToggle
Protection typeWithout protection
Main product or component typeBasic frame
Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui800 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C

All specifications

C16B3 additional specifications
ParameterValue
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth86 mm
Width105 mm
Height161 mm
Electrical life cycles40000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2 15000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2 20000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2 7500 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2
Mechanical life cycles40000 cycles conforming to IEC 60947-2
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The Schneider Electric C16B3 is a ComPacT NSX160B basic frame — a 3-pole MCCB rated 160 A at 40 °C, without a trip unit. This means you select and install the trip unit separately (thermal-magnetic or electronic), so the frame itself is a fixed mechanical base with a 160 A continuous current capacity. The 25 kA Icu at 380/415 V AC (50/60 Hz) per IEC 60947-2 tells you it can safely interrupt a fault current up to that level without failing, which is the standard for commercial and light industrial distribution panels.

Mounting and integration — fixed backplate, front connections

Mounts fixed to a backplate (not DIN rail) with a 35 mm connection pitch. Front-facing upside and downside connections simplify busbar or cable routing in a panel. The 105 mm width, 161 mm height, and 86 mm depth fit standard enclosure layouts for 160 A frames. IP40 front-face protection and IK07 impact resistance suit indoor panel environments.

Electrical durability and isolation capability

Rated for 40,000 mechanical cycles and 40,000 electrical cycles at 440 V AC at rated current (In). At 690 V AC, electrical durability drops to 7,500 cycles at In — expect shorter life on higher-voltage motor loads. The frame is certified for isolation (suitability for isolation per EN/IEC 60947-2), meaning it can be used as a disconnecting means with a visible break.

MPN