Skip to main content
Schneider Electric C16F2TM160

Schneider Electric C16F2TM160 ComPacT NSX160F, 160 A, 18 kA

MPN C16F2TM160
Active

Schneider Electric, ComPacT NSX series, NSX160F, circuit breaker, 2-pole, 160 A, thermal-magnetic TM-D trip unit, 18 kA Icu at 415 V AC, EN/IEC 60947-2.

$3.82 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C16F2TM160 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz 500 V DC
Insulation voltage ui750 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity36 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 380/415 V AC 50/60 Hz 1P conforming to IEC 60947-2 15 kA Icu at 440 V AC 50/60 Hz 1P conforming to IEC 60947-2 10 kA Icu at 500/525 V AC 50/60 Hz 2P conforming to IEC 60947-2 5 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 250 V DC 50/60 Hz 1 pole conforming to IEC 60947-2 36 kA Icu at 500 V DC 50/60 Hz 2 poles in series conforming to IEC 60947-2
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C

All specifications

C16F2TM160 additional specifications
ParameterValue
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth86 mm
Width70 mm
Height161 mm
Electrical life cycles20000 cycles at 277 V In/2 10000 cycles at 277 V In
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The C16F2TM160 is a Schneider Electric ComPacT NSX160F molded-case circuit breaker, 2-pole, with a fixed TM-D thermal-magnetic trip unit rated 160 A at 40 °C. For a 2-pole distribution breaker in a panel, that 18 kA at 415 V covers most secondary-side faults on a typical 400 V supply; the 36 kA at 240 V AC and 250 V DC ratings handle higher available fault currents on lower-voltage legs. The TM-D trip gives you thermal overload protection (L) and magnetic short-circuit protection (I) in one unit — no extra modules to fit.

Fixed-mount on a backplate, 70 mm wide, 161 mm tall, 86 mm deep. Front-connected both sides, so you land the line and load cables on the same face — handy when the breaker is deep in a panel and you don't want to reach around the back. IP40 front face keeps tools and fingers out. The toggle handle is the control type — manual on/off, no aux contacts fitted as standard.

MPN
C16F2TM160