Specifications

C16F47E160 key specifications
ParameterValue
Control typeToggle
Display typeLCD display
Trip unit typeElectronic
Main product or component typeEarth leakage circuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui500 V AC 50/60 Hz
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 35 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C

All specifications

C16F47E160 additional specifications
ParameterValue
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degreeclass 3
Depth86 mm
Width140 mm
Height161 mm
Electrical life cycles40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In
Mechanical life cycles40000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

MCCB with integrated earth-leakage protection

The Schneider Electric C16F47E160 is a ComPacT NSX160F moulded-case circuit breaker with a MicroLogic 7.2 E electronic trip unit, rated 160 A at 40 °C. This 4-pole unit combines overload (L), short-time short-circuit (S), instantaneous short-circuit (I), and earth-leakage (R) protection in one device — the R function eliminates the need for a separate earth-leakage relay and toroid, saving panel space and wiring. Breaking capacity is 85 kA Icu at 240 V AC and 36 kA Icu at 415 V AC per IEC 60947-2, which covers most industrial distribution boards and motor control centres. The LCD display on the trip unit shows metered values, alarm logs, and maintenance indicators, so you can read load current and event history without opening the door.

Selectivity and coordination

The 36 kA Icu at 415 V AC puts this breaker in the F breaking-capacity class, which coordinates downstream with standard NSX100/160 feeders and upstream with a Compact NS630b or Masterpact NT. The MicroLogic 7.2 E trip unit offers adjustable L, S, I, and R curves, so you can set the short-time delay (S) to achieve full selectivity with downstream devices rated up to 160 A.

Panel integration

The 140 mm width and 161 mm height fit standard ComPacT NSX cutouts; the 86 mm depth leaves clearance for rear-mounted accessories. The toggle control and LCD display are accessible from the front.

MPN