C16S4 key specifications
ParameterValue
Control typeToggle
Protection typeWithout protection
Main product or component typeBasic frame
Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui800 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity100 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 120 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 90 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C

All specifications

C16S4 additional specifications
ParameterValue
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth86 mm
Width140 mm
Height161 mm
Electrical life cycles40000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2 15000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2 20000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2 7500 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2
Mechanical life cycles40000 cycles conforming to IEC 60947-2
ApplicationDistribution
Operating temperature-25...70 °C

Product details

It is rated 100 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2, which means it can safely interrupt a fault up to that level without welding contacts or cascading upstream. The 160 A frame rating at 40 °C sets the continuous current limit for the assembly; the actual trip curve comes from the plug-in trip unit (not included).

Breaking capacity is the headline figure: 100 kA Icu at 415 V AC, with 120 kA at 240 V and 90 kA at 440 V. The Ics (service breaking capacity) matches the Icu at every voltage level — meaning the frame can be reclosed after a fault at full rated current without derating, a requirement for main incomer duty in many panel designs. The 8 kV impulse withstand voltage (Uimp) and overvoltage category III confirm it is built for fixed-installation distribution boards, not plug-in equipment. Mechanical durability is 40,000 cycles; electrical durability ranges from 40,000 cycles at 440 V at half rated current down to 7,500 cycles at 690 V at full rated current.

Fixed mounting on a backplate, 140 mm wide × 161 mm high × 86 mm deep. The 35 mm connection pitch and front-connect terminals (both upside and downside) suit standard panel layouts with busbar or cable entry from the front. IP40 enclosure protection means it is suitable for indoor switchboards where no water spray is present; the IK07 impact rating handles incidental tool contact during installation.