Schneider Electric C256TM160C

Schneider Electric C256TM160C ComPacT NSX250 TM-D Trip Unit,

MPN C256TM160C
Active

Schneider Electric ComPacT NSX250, TM-D trip unit, thermal-magnetic, 160 A at 50 °C, 4 poles 3D, LI protection, EN/IEC 60947-2.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C256TM160C specifications
ParameterValue
Trip unit typeThermal-magnetic
Main product or component typeTrip unit
Voltage690 V AC 50/60 Hz 750 V DC
IP ratingIP40
Temp storage max85 °C
Temp storage min-50 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degree3 conforming to IEC 60947-1
ApplicationDistribution
Operating temperature-25...70 °C

Product details

It is rated 160 A at 50 °C, with 4 poles configured as 3D (three protected poles, neutral left position with no protection). The LI protection curve covers overload (thermal, adjustable Ir from 0.7 to 1 x In) and short-circuit (magnetic, fixed Ii at 1250 A). This is the drop-in trip unit that defines the breaker's protection settings — you swap it into the NSX250 frame, not the whole breaker.

If your panel runs hotter, you derate — the TM-D's thermal element responds to both load current and ambient temperature. The fixed instantaneous trip at 1250 A (about 7.8 x In) means it clears bolted faults fast, but you lose the ability to dial up the magnetic pickup for high-inrush loads like large motors. The adjustable long-time pickup (Ir) lets you fine-tune the overload threshold between 112 A and 160 A, which is useful when the connected load is smaller than the frame rating.

Where it fits and how it mounts

This trip unit mounts into the ComPacT NSX250 fixed breaker. The breaker itself is DIN-rail or screw-panel mount, depending on the base.

Electrical shock protection class II — double-insulated, no earth connection needed.

MPN