Skip to main content
Schneider Electric C25B47E250

Schneider C25B47E250 ComPacT NSX 4-pole MCCB, 250 A, 40 kA

MPN C25B47E250
Active

Schneider Electric ComPacT NSX C25B47E250 molded case circuit breaker, 4 poles, 250 A rated current, 40 kA Icu at 440 V AC, MicroLogic 7.2 E electronic trip unit, earth-leakage protection, fixed mount, IEC 60947-2.

$1,259.63 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C25B47E250 key specifications
ParameterValue
Control typeToggle
Display typeLCD display
Trip unit typeElectronic
Main product or component typeEarth leakage circuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui500 V AC 50/60 Hz
Breaking capacity40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C

All specifications

C25B47E250 additional specifications
ParameterValue
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degreeclass 3
Depth86 mm
Width140 mm
Height161 mm
Electrical life cycles20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

Overview

The C25B47E250 is a Schneider ComPacT NSX 4-pole molded case circuit breaker rated 250 A with a 40 kA breaking capacity at 440 V AC, fitted with a MicroLogic 7.2 E electronic trip unit. The trip unit provides LSI+R protection: overload (L), short-time short-circuit (S), instantaneous (I), and earth-leakage (R), making it suited for distribution panels requiring ground-fault detection.

Compared to the 3-pole C25N3 (85 kA at 690 V, basic frame), the C25B47E250 adds a fourth pole and earth-leakage protection but at a lower 40 kA Icu at 440 V. Choose the C25N3 when the BOM specifies a 3-pole basic frame with higher interrupting capacity; pick the C25B47E250 when a 4-pole earth-leakage MCCB is required.

MPN
C25B47E250