Skip to main content
Schneider Electric C4047E400

Schneider C4047E400 MicroLogic 7.3 E Trip Unit, 400 A

MPN C4047E400
Active

Schneider Electric ComPacT NSX series, MicroLogic 7.3 E electronic trip unit, 400 A at 40 °C, 4P, LSIR protection with integrated earth-leakage, LCD display, EN/IEC 60947-2.

$24.40 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C4047E400 specifications
ParameterValue
Display typeLCD display
Trip unit typeElectronic
Main product or component typeTrip unit
Voltage440 V AC 50/60 Hz
IP ratingIP40
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degree3 conforming to IEC 60947-1
ApplicationDistribution
Operating temperature-25...70 °C

Product details

Trip unit for a 400 A distribution feeder

The Schneider Electric C4047E400 is a MicroLogic 7.3 E electronic trip unit for the ComPacT NSX400...630 molded-case circuit breaker platform. It is rated 400 A at 40 °C (Ir adjustable 160...400 A) and provides LSIR protection: long-time overload (L), short-time short-circuit (S), instantaneous (I), and integrated earth-leakage (R) — all configurable through the onboard LCD display.

What the LSIR settings mean for coordination

The L protection (long-time) pick-up is adjustable 160...400 A with a delay from 15...400 s at 1.5 x Ir — that range lets you set the feeder to ride through motor inrush without nuisance tripping, while still clearing a sustained overload. The S protection (short-time) delay is 0...0.4 s with I²t on or off; turning I²t on gives inverse-time selectivity downstream, off gives fixed-time coordination. The I (instantaneous) pick-up is also adjustable, and the R (earth-leakage) is Class A, adjustable via the rotary switch on the front face.

Thermal memory and data logging

The unit also logs energy metering, time-stamped events, and demand values, accessible through the LCD or via the communication data port.

Environmental and installation limits

Rated for -25...70 °C operating ambient and -40...85 °C storage. IP40 front face. The unit is Class II double-insulated, so no separate protective-earth connection is required on the trip unit itself.

MPN