Skip to main content
Schneider Electric C40H32D250

C40H32D250 ComPacT NSX 250A 3P Circuit Breaker, 70kA 415V

MPN C40H32D250
Active

Schneider Electric ComPacT NSX, NSX400H frame, 3-pole circuit breaker, 250 A MicroLogic 2.3 electronic trip unit, 70 kA Icu at 415 V AC, toggle control.

$833.26 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C40H32D250 key specifications
ParameterValue
Control typeToggle
Trip unit typeElectronic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz
Breaking capacity100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 65 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 20 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
IP ratingIP40
Terminal pitch45 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C

All specifications

C40H32D250 additional specifications
ParameterValue
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth110 mm
Width140 mm
Height255 mm
Electrical life cycles12000 cycles at 440 V In/2 6000 cycles at 440 V In 6000 cycles at 690 V In/2 3000 cycles at 690 V In
Mechanical life cycles15000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The C40H32D250 is a Schneider Electric ComPacT NSX circuit breaker in the NSX400H frame, 3-pole, with a MicroLogic 2.3 electronic trip unit rated 250 A at 40 °C. It's a distribution breaker, not a motor-circuit protector — the trip unit gives you LSI protection: long-time overload (L), short-time short-circuit with fixed delay (So), and instantaneous short-circuit (I). That makes it a good fit for main or feeder breakers in a panel where you need selective coordination downstream. That's the kind of detail that matters when you're protecting a transformer or a long cable run that takes time to cool.

But the full curve matters more. At 240 V AC you get 100 kA Icu; at 480 V AC (UL rating) it's 65 kA; at 600 V AC it drops to 20 kA. If your system fault current is, say, 85 kA at 240 V, this breaker handles it. But at 480 V you need to stay under 65 kA. That's the kind of thing a site electrical engineer checks against the utility's fault study before committing the BOM line.

Mounting and environment — panel integration notes

Mounts on a backplate, front-connected both top and bottom. Connection pitch is 45 mm. It can be mounted horizontal, vertical, or flat on the back, which gives flexibility in tight enclosures.

Durability — how many operations before replacement

Mechanical durability is 15,000 cycles. Electrical durability depends on the load: 12,000 cycles at 440 V at half rated current (In/2), 6,000 cycles at 440 V at full In, and 3,000 cycles at 690 V at full In. If this breaker is in a frequent-switching application like a capacitor bank or a welding line, those numbers tell you when to plan a replacement.

MPN
C40H32D250