Specifications

C40H32D400 key specifications
ParameterValue
Control typeToggle
Trip unit typeElectronic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz
Breaking capacity100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 65 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 20 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
IP ratingIP40
Terminal pitch45 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C

All specifications

C40H32D400 additional specifications
ParameterValue
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth110 mm
Width140 mm
Height255 mm
Electrical life cycles12000 cycles at 440 V In/2 6000 cycles at 440 V In 6000 cycles at 690 V In/2 3000 cycles at 690 V In
Mechanical life cycles15000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

It carries a 400 A MicroLogic 2.3 electronic trip unit with L-So-I protection curves — long-time overload, short-time short-circuit with fixed delay, and instantaneous — so you get adjustable coordination without swapping trip packs. At 255 x 140 x 110 mm (H x W x D) and IP40 front-face protection, it fits backplate-mounted enclosures where you need front-access cabling on both line and load sides. The IK07 impact rating means it can take a knock during panel wiring or service without cracking the case.

Breaking capacity — what the H suffix buys you

At 240 V it's rated 100 kA Icu, and at 480 V it still holds 65 kA Icu under UL 60947-4-1. For a 400 A frame, that headroom handles most industrial transformer-fed buswork without cascading upstream breakers; you can size the main for selectivity rather than brute-force interrupting rating. The electronic trip unit (MicroLogic 2.3) includes thermal memory — it remembers the last 20 minutes of heating before and after a trip, so a hot reclose won't nuisance-trip on a motor inrush that a cold breaker would handle. That matters on pump or compressor circuits where restarts happen fast.

Mounts flat on the backplate in both horizontal and vertical orientations — no derating for position as long as the 40 °C ambient rating is respected. Six accessory slots (aux contacts, shunt trip, under-voltage release, motor mechanism) can be populated without removing the breaker from the panel. No earth-leakage protection built in — if you need ground-fault on the same frame, you'd step to the MicroLogic 2.3M or add an external Vigi module. The toggle control is manual; no motor operator included, but the six-slot complement allows one to be retrofitted.