Skip to main content
Schneider Electric C40N31M320

Schneider Electric C40N31M320 ComPacT NSX400N, 320 A, 85 kA

MPN C40N31M320
Active

Schneider Electric ComPacT NSX400N, circuit breaker, 3P, 320 A, MicroLogic 1.3 M electronic trip unit, 85 kA Icu at 240 V AC, motor protection.

$709.19 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C40N31M320 key specifications
ParameterValue
Control typeToggle
Trip unit typeElectronic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz
IP ratingIP40
Terminal pitch45 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C
Temp operating max70 °C

All specifications

C40N31M320 additional specifications
ParameterValue
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth110 mm
Width140 mm
Height255 mm
Electrical life cycles12000 cycles at 440 V In/2 6000 cycles at 440 V In 6000 cycles at 690 V In/2 3000 cycles at 690 V In
Mechanical life cycles15000 cycles
ApplicationMotor protection
Operating temperature-25...70 °C

Product details

Schneider Electric C40N31M320 is a ComPacT NSX400N molded-case circuit breaker, 3-pole, rated 320 A at 65 °C with a MicroLogic 1.3 M electronic trip unit. It's built for motor protection — the 'M' in the trip unit designation means it carries motor-specific curves for starting inrush and overload. Backplate-mounted, front-connected, and toggle-operated, it fits a standard panel layout with 140 mm width and 255 mm height.

At 480 V AC it still holds 50 kA Icu, so it coordinates cleanly with downstream 18 kA or 25 kA rated feeders. The 85 kA at 240 V AC is the high side for 208/240 V distribution. Utilisation category A means it's not intended for frequent switching under load — that's the contactor's job. It's a protection device first.

Trip unit and motor protection

The S curve lets you set a deliberate delay for selectivity with downstream breakers — you can let a branch fault clear before the main trips. The I curve handles the short-circuit instant. Because it's electronic, it holds its calibration over temperature better than a thermal-magnetic unit. Power dissipation is 12.29 W per pole — factor that into your enclosure cooling calculation.

Physical integration

Mounts on a backplate — no DIN rail. Front connections top and bottom, 45 mm connection pitch. Six accessory slots for shunt trips, aux contacts, or communication modules. IP40 enclosure protection, IK07 impact resistance. Horizontal or vertical mounting allowed, flat on the back.

MPN