Schneider Electric C60H4P3AD

C60H4P3AD MCB, 4P, D Curve, 3 A, 10 kA, Multi9

MPN C60H4P3AD
Obsolete

Schneider Electric Multi9 C60H, C60H4P3AD, 4-pole miniature circuit breaker, D curve, 3 A rated current, 10 kA breaking capacity at 230/400 V AC, DIN rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C60H4P3AD specifications
ParameterValue
Control typeToggle
Network typeDC AC
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage12...440 V AC 50/60 Hz
Insulation voltage ui500 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity10 kA Icn at 230/400 V AC 50/60 Hz conforming to EN 60898 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to IEC 60947-2 50 kA Icu at 250 V DC 4P conforming to IEC 60947-2
Temp storage max70 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-25 °C
Storage temperature-40...70 °C
Depth73 mm
Width72 mm
Height81 mm
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...60 °C

Product details

The Schneider Electric C60H4P3AD is a 4-pole miniature circuit breaker from the Multi9 C60H series, rated 3 A at 40 °C with a D tripping curve.

Under IEC 60947-2, the ultimate breaking capacity (Icu) reaches 15 kA at 400...415 V AC, 30 kA at 230...240 V AC, and 40 kA at 125 V DC for 3-pole connection. The service breaking capacity (Ics) is 7.5 kA at 230/400 V AC per EN 60898, confirming the breaker clears faults repeatedly within its rating.

Occupies 8 modules of 9 mm pitch on the DIN rail — 72 mm wide, 81 mm tall, 73 mm deep. The toggle provides local ON/OFF indication with a contact position indicator for isolation verification per IEC 60947-2. Separate earth-leakage protection block can be added alongside.

MPN
C60H4P3AD