Schneider Electric C6347E570 ComPacT NSX MicroLogic 7.3 E Tr

MPN C6347E570
Active

Schneider Electric ComPacT NSX400...630, MicroLogic 7.3 E electronic trip unit, 570 A at 40 °C, 4P, LSIR protection, LCD display, EN/IEC 60947-2.

$24.40 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C6347E570 specifications
ParameterValue
Display typeLCD display
Trip unit typeElectronic
Main product or component typeTrip unit
Voltage440 V AC 50/60 Hz
IP ratingIP40
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degree3 conforming to IEC 60947-1
ApplicationDistribution
Operating temperature-25...70 °C

Product details

MicroLogic 7.3 E Trip Unit for ComPacT NSX — 570 A, LSIR Protection

The Schneider Electric C6347E570 is a MicroLogic 7.3 E electronic trip unit for the ComPacT NSX400...630 range, rated 570 A at 40 °C. It provides LSIR protection — long-time (L), short-time (S), instantaneous (I), and earth-leakage (R) — meeting EN/IEC 60947-2 for distribution applications. The 4-pole unit includes an integrated earth-leakage protection (Class A) and an LCD display for metering and event logs. A 20-minute thermal memory before and after tripping ensures coordination on reclose cycles, critical for keeping a weld line or conveyor string running without nuisance trips.

Protection Functions and Adjustability

Long-time pick-up (Ir) adjusts from 250 to 570 A, with delay tr settable 15–400 s at 1.5×Ir, 0.35–11 s at 7.2×Ir, or 0.5–16 s at 6×Ir. Short-time pick-up (Isd) is adjustable, with delay tsd from 0 to 0.4 s (I²t off) or 0.1 to 0.4 s (I²t on). Instantaneous protection (Ii) is also adjustable. Earth-leakage can be disabled via the IΔn rotary switch. Neutral protection offers four configurations: 3D + N/2, 4D, 3D + OSN, or no protection.

Communication, Metering, and Signalling

The trip unit reports protection and alarm settings, energy metering, demand current and power, power quality, earth-leakage current, time-stamped histories and event tables, instantaneous and demand values, maximeters/minimeters, maintenance indicators, and test reports. Local signalling includes a flashing green LED for ready-to-operate, a red LED at 105% Ir for overload, and an orange LED at 90% Ir for pre-alarm. The LCD display supports on-device interrogation of all these metrics.

Environmental and Installation Ratings

IP40 front-of-panel protection (IEC 60529) keeps out tools and dust. The unit is Class II electrically (double-insulated), fixed-mount, with neutral on the left. No zone selective interlocking (ZSI) is provided.

MPN