Schneider Electric EasyPact NW, circuit breaker, ENW24102, 3P, 1000 A at 40 °C, 50 kA Icu at 440 V AC, drawout mounting, IP40.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW24102 key specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity50 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Utilization categoryCategory B
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-5 °C

All specifications

ENW24102 additional specifications
ParameterValue
Pollution degree4 conforming to IEC 60664-1
Depth395 mm
Width441 mm
Height439 mm
Mechanical life cycles20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
ApplicationDistribution
Operating temperature-5...60 °C

Product details

What this 1000 A drawout breaker is for

It carries a 50 kA Icu breaking capacity at 440 V AC and 42 kA at 690 V AC, both per IEC 60947-2 — that means it clears faults at those levels without the arc re-striking, which is what you need for main or feeder protection in a plant where fault currents can hit that range. Drawout mounting lets you rack the breaker out for maintenance without disconnecting power cables, a standard feature for switchgear where uptime matters.

The IP40 enclosure keeps tools and fingers out but doesn't seal against water — mount it in a cabinet.

Drawout mounting on rails, rear-connected at 115 mm pitch without spreader. Dimensions are 441 mm wide by 439 mm high by 395 mm deep — that's a substantial footprint, so check the switchgear cell size before committing. The control is push-button operated with a contact position indicator. Mechanical durability is 20,000 cycles with maintenance, 10,000 without — for a main breaker that's cycled infrequently, that's plenty; for a frequently switched load, consider the electrical durability: 6,000 cycles at 440 V, 4,000 at 690 V without maintenance.