Schneider Electric ENW24117

Schneider Electric ENW24117 EasyPact NW Circuit Breaker, 800

MPN ENW24117
Active

Schneider Electric EasyPact NW, air circuit breaker, ENW24117, 800 A at 40 °C, 4-pole drawout, 50 kA Icu at 440 V AC, IEC 60947-2.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW24117 specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-2
Utilization categoryCategory B
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-5 °C
Pollution degree4 conforming to IEC 60664-1
Depth395 mm
Width556 mm
Height439 mm
ApplicationDistribution
Operating temperature-5...60 °C

Product details

The Schneider Electric ENW24117 is an EasyPact NW air circuit breaker rated 800 A at 40 °C, four-pole (4P 4d), with a drawout mounting that lets you rack the breaker out for maintenance without pulling the main bus. It's built to IEC 60947-2, the standard for low-voltage switchgear, and carries a 50 kA Icu at 220...440 V AC (42 kA at 690 V AC) — so it handles hard faults on a distribution board without welding its contacts shut. The 1000 V rated insulation voltage and pollution degree 4 rating mean it's comfortable in industrial environments where dust and humidity are part of the landscape. This breaker is a Category B device, which means it's designed for selective coordination — it can hold through a downstream short-time delay so the fault clears closer to the load, keeping the rest of the plant live. Mechanical durability is 20,000 cycles with maintenance (10,000 without), and electrical durability runs 6,000 cycles at 440 V AC without maintenance. That's a solid lifespan for a main or feeder breaker in a factory distribution panel.

The ENW24117 mounts on a rail in a drawout cradle, so it's sized for a switchboard lineup — you don't bolt it direct to a panel backplate. Its footprint is 556 mm wide by 439 mm high by 395 mm deep, and connections are rear-mounted, horizontal or vertical, with a 115 mm pitch without spreader. Neutral sits on the left, and the neutral protection setting is configurable: no protection (3D), 0.5 x Ir (3D + N/2), or 1 x Ir (4D) — something to flag when you're ordering to match an existing setup.

The 25 ms maximum breaking time tells you the arc is quenched fast enough to limit thermal damage in the bus bars.