Skip to main content
Schneider Electric ENW24181

Schneider Electric ENW24181 EasyPact NW Switch Disconnector,

MPN ENW24181
Active

Schneider Electric EasyPact NW ENW24181 switch disconnector, 800 A AC-23A, 690 V AC, 4 poles, drawout, rear-connected, IP40.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW24181 key specifications
ParameterValue
Control typePush-button
Main product or component typeSwitch disconnector
Voltage690 V AC 50/60 Hz conforming to IEC 60947-3
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-3
CurrentAC-23 A: 800 A AC 50/60 Hz 690 V
Utilization categoryAC-23 A
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-5 °C

All specifications

ENW24181 additional specifications
ParameterValue
Storage temperature-40...85 °C without control unit
Pollution degree4 conforming to IEC 60664-1
Depth395 mm
Width556 mm
Height439 mm
Mechanical life cycles20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3
ApplicationDistribution
Operating temperature-5...70 °C

Product details

The Schneider Electric ENW24181 is a 4-pole switch disconnector from the EasyPact NW range, rated 800 A in AC-23A utilisation category at 690 V AC — meaning it handles motor switching and mixed resistive-inductive loads with frequent making and breaking, not just isolation. It is certified to IEC 60947-3 and carries a suitability-for-isolation marking, so it doubles as a visible-break disconnect for lockout-tagout procedures. Rated short-time withstand current (Icw) is 50 kA for 1 s or 25 kA for 3 s, and short-circuit making capacity (Icm) hits 105 kA peak — figures that matter for coordination with upstream protection and for verifying the switch can close onto a fault without welding contacts.

Drawout (withdrawal) mounting on a rail — the switch chassis slides out for inspection or replacement without disturbing the fixed rear connections. Connection pitch is 115 mm without spreader, neutral on the left, and rear connection location suits panel layouts where front access is limited. IP40 enclosure protection keeps tools and fingers out but is not rated for washdown — install inside a cabinet or switchgear cubicle. Dimensions: 556 mm wide, 439 mm high, 395 mm deep — verify cutout and swing-clear space before panel layout.

Durability and operating conditions

Mechanical durability: 20,000 cycles with maintenance, 10,000 without. Electrical durability at AC-23A: 6,000 cycles at 440 V, 4,000 cycles at 690 V. These numbers drive the preventive replacement interval in high-cycle applications like crane or conveyor disconnects. Continuous rated duty — no derating needed for sustained load.

MPN
ENW24181