Skip to main content
Schneider Electric ENW24191

Schneider Electric ENW24191 EasyPact NW Switch Disconnector,

MPN ENW24191
Active

Schneider Electric EasyPact NW switch disconnector, ENW24191, 1250 A AC-23A, 4 poles, fixed mount, 690 V AC, IP40.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW24191 key specifications
ParameterValue
Control typePush-button
Main product or component typeSwitch disconnector
Voltage690 V AC 50/60 Hz conforming to IEC 60947-3
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-3
CurrentAC-23 A: 1250 A AC 50/60 Hz 690 V
Utilization categoryAC-23 A
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-5 °C

All specifications

ENW24191 additional specifications
ParameterValue
Storage temperature-40...85 °C without control unit
Pollution degree4 conforming to IEC 60664-1
Depth297 mm
Width537 mm
Height352 mm
ApplicationDistribution
Operating temperature-5...70 °C

Product details

The Schneider Electric ENW24191 is a 4-pole fixed-mount switch disconnector from the EasyPact NW range, rated 1250 A in AC-23A duty at 690 V AC. It's also marked suitable for isolation per IEC 60947-3, so you can use it as a visible-break disconnecting means for a panel or machine.

Ratings that matter for the panel

The 1250 A rating at 690 V AC is the headline number, but the short-time withstand (Icw) tells you how it handles a fault before the upstream breaker clears: 50 kA for 1 second, or 25 kA for 3 seconds, per IEC 60947-3. That's the figure your coordination study uses. The making capacity (Icm) is 105 kA peak — meaning it can close onto a bolted fault without welding its contacts. Impulse withstand (Uimp) is 12 kV, which covers most 690 V industrial installations. Pollution degree 4 per IEC 60664-1 means it's rated for harsh environments with conductive dust or condensation — not just a clean control room.

Physical fit and mounting

Fixed-mount on a base plate, rear-connected. The footprint is 537 mm wide by 352 mm tall by 297 mm deep — that depth matters if you're shoehorning it into an existing enclosure with limited clearance behind the door. Connection pitch is 115 mm without a spreader. Neutral position is left.

MPN