Skip to main content
Schneider Electric ENW24195

Schneider Electric ENW24195 EasyPact NW Switch Disconnector,

MPN ENW24195
Active

Schneider Electric EasyPact NW switch disconnector, ENW24195, 3200 A AC-23A, 690 V, 4 poles, fixed mounting, IP40, IEC 60947-3.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW24195 key specifications
ParameterValue
Control typePush-button
Main product or component typeSwitch disconnector
Voltage690 V AC 50/60 Hz conforming to IEC 60947-3
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-3
CurrentAC-23 A: 3200 A AC 50/60 Hz 690 V
Utilization categoryAC-23 A
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-5 °C

All specifications

ENW24195 additional specifications
ParameterValue
Storage temperature-40...85 °C without control unit
Pollution degree4 conforming to IEC 60664-1
Depth297 mm
Width537 mm
Height352 mm
Mechanical life cycles20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3
ApplicationDistribution
Operating temperature-5...70 °C

Product details

The Schneider Electric ENW24195 is a fixed-mount switch disconnector from the EasyPact NW range, rated for 3200 A in AC-23A duty at 690 V AC, 4 poles, with the neutral on the left. It's built for distribution applications where you need a visible-break isolator that meets IEC 60947-3 for isolation — the suitability-for-isolation marking is on the nameplate, so it qualifies as a lockable disconnect point for safe maintenance access.

The 3200 A AC-23A rating is the motor-switching current — that's the heavy lifting for starting and stopping motor loads, not just resistive heating. The short-time withstand (Icw) is 50 kA for 1 second or 25 kA for 3 seconds, and the making capacity (Icm) is 105 kA peak — that's the fault-closing rating if you close onto a bolted fault.

MPN