Skip to main content
Schneider Electric ENW24214

ENW24214 EasyPact NW Switch Disconnector, 1000 A, 4P, Drawou

MPN ENW24214
Active

Schneider Electric EasyPact NW series, ENW24214 switch disconnector, 1000 A AC-23A, 690 V, 4 poles, drawout mounting, IP40.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW24214 key specifications
ParameterValue
Control typePush-button
Main product or component typeSwitch disconnector
Voltage690 V AC 50/60 Hz conforming to IEC 60947-3
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-3
CurrentAC-23 A: 1000 A AC 50/60 Hz 690 V
Utilization categoryAC-23 A
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-5 °C

All specifications

ENW24214 additional specifications
ParameterValue
Storage temperature-40...85 °C without control unit
Pollution degree4 conforming to IEC 60664-1
Depth395 mm
Width556 mm
Height439 mm
Mechanical life cycles20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3
ApplicationDistribution
Operating temperature-5...70 °C

Product details

The ENW24214 is a 1000 A switch disconnector from the Schneider Electric EasyPact NW range, built for distribution duty in industrial switchboards. Four poles, drawout chassis, rear-connected — this is the piece that isolates a feeder or a large motor circuit for maintenance, with a contact position indicator so you can see the gap from outside the panel.

Rated 1000 A in AC-23A utilisation category at 690 V — that covers motor loads with occasional inrush, not just resistive heating. AC-23A is the heavy lifting category under IEC 60947-3: switching motors, transformers, and capacitive loads where the making and breaking current is higher than a plain disconnect. The 66 kA short-time withstand for 1 second and 143 kA making capacity tell you this thing can sit through a fault and close onto one without welding its contacts — critical for selectivity coordination downstream of a transformer. The IP40 enclosure keeps tools and fingers out but breathes; in a dirty environment the drawout cassette seals the arc chamber when racked in. Rated insulation voltage 1000 V and impulse withstand 12 kV give headroom for 690 V systems with decent surge exposure.

MPN
ENW24214