Schneider Electric ENW24260

Schneider Electric ENW24260 EasyPact NW Circuit Breaker, 400

MPN ENW24260
Active

Schneider Electric EasyPact NW, circuit breaker, ENW24260, 4000 A at 40 °C, 66 kA Icu at 440 V AC, 4P, IP40, IEC 60947-2.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW24260 key specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Utilization categoryCategory B
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-5 °C

All specifications

ENW24260 additional specifications
ParameterValue
Pollution degree4 conforming to IEC 60664-1
Depth297 mm
Width537 mm
Height352 mm
Mechanical life cycles20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
ApplicationDistribution
Operating temperature-5...60 °C

Product details

4000 A distribution breaker, EasyPact NW series

Its 66 kA Icu at 220...440 V AC (50/60 Hz) per IEC 60947-2 means it can safely interrupt fault currents up to that level without upstream cascading — a figure that governs the SCCR headroom for the entire panel. At 690 V AC the breaking capacity holds at 50 kA Icu, with a corresponding Ics of 50 kA, so the breaker clears service faults and remains usable afterward within that range. Rated insulation voltage is 1000 V AC, operational voltage 690 V AC, with an impulse withstand of 12 kV. Pollution degree 4 per IEC 60664-1 is the harshest standard — conductive pollution is expected, so the creepage distances are designed for industrial environments where dust, moisture, or condensation are present.

Mechanical and electrical endurance

Electrical durability is rated 5000 cycles at 440 V AC without maintenance (Category B per IEC 60947-2), and 2500 cycles at 690 V AC. Mechanical durability reaches 20000 cycles with maintenance, 10000 without. Maximum breaking time is 25 ms; maximum closing response time is 70 ms. These figures matter for coordination studies — the 25 ms clearing time sets the lower bound for downstream device let-through.