Skip to main content
Schneider Electric ENW24267

Schneider Electric ENW24267 EasyPact NW Switch Disconnector,

MPN ENW24267
Active

Schneider Electric EasyPact NW switch disconnector, ENW24267, 3200 A AC-23A, 690 V AC, 4 poles, drawout, IP40, rear connection.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW24267 key specifications
ParameterValue
Control typePush-button
Main product or component typeSwitch disconnector
Voltage690 V AC 50/60 Hz conforming to IEC 60947-3
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-3
CurrentAC-23 A: 3200 A AC 50/60 Hz 690 V
Utilization categoryAC-23 A
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-5 °C

All specifications

ENW24267 additional specifications
ParameterValue
Storage temperature-40...85 °C without control unit
Pollution degree4 conforming to IEC 60664-1
Depth395 mm
Width556 mm
Height439 mm
Mechanical life cycles20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3
ApplicationDistribution
Operating temperature-5...70 °C

Product details

The Schneider Electric ENW24267 is a 4-pole switch disconnector from the EasyPact NW range, rated for 3200 A in AC-23A utilisation category at 690 V AC — meaning it handles heavy motor and mixed loads with frequent switching, not just resistive isolation. Drawout mounting lets you rack the unit out for maintenance without disturbing the rear-connected busbars.

The headline 3200 A AC-23A rating is the operational current for switching motor loads and mixed inductive/resistive circuits — not a continuous bus rating. For pure isolation duty (no load make/break), the same switch is suitable per IEC 60947-3. Short-time withstand of 50 kA for 1 second (or 25 kA for 3 seconds) tells you the switch can ride through a fault long enough for an upstream breaker to clear, so coordination studies should check that the let-through energy stays within the switch's I²t capability. The 105 kA making capacity (Icm) confirms it can close onto a short circuit without welding contacts — critical for a main incoming switch.

Integration notes

Drawout chassis mounts on a rail with rear horizontal or vertical connection positions. The neutral is on the right. Connection pitch is 115 mm without a spreader. IP40 front face keeps out tools and fingers but not water — install in a dry indoor enclosure. Mechanical durability: 20000 cycles with maintenance, 10000 without. Electrical durability for AC-23A: 5000 cycles at 440 V, 2500 cycles at 690 V.

MPN
ENW24267