Skip to main content
Schneider Electric EVS20H3MW20

Schneider Electric EVS20H3MW20 EasyPact EVS Circuit Breaker,

MPN EVS20H3MW20
Active

Schneider Electric EasyPact EVS series, EVS20H3MW20, 3-pole drawout circuit breaker, 2000 A rated current, 65 kA breaking capacity at 440 V AC, IEC 60947-2.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

EVS20H3MW20 key specifications
ParameterValue
Control typeManually operated
Trip unit typeElectronic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity65 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Utilization categoryCategory B
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C

All specifications

EVS20H3MW20 additional specifications
ParameterValue
Temp operating min-5 °C
Pollution degree4 conforming to IEC 60664-1
Depth395 mm
Width441 mm
Height439 mm
Mechanical life cycles20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
ApplicationDistribution
Operating temperature-5...70 °C

Product details

Panel integration note — EVS20H3MW20

The Schneider Electric EVS20H3MW20 is a 3-pole drawout circuit breaker from the EasyPact EVS family, rated 2000 A at 40 °C with a 65 kA Icu breaking capacity at 220...440 V AC 50/60 Hz per IEC 60947-2. The drawout mounting and rear connection position mean the breaker slides onto a rail base plate — no need to disconnect main power cables during swap-out, which cuts downtime on a 2000 A feeder.

The 2000 A trip unit rating and 65 kA Icu at 440 V tell you this breaker handles main or heavy feeder duty in a 480 V class distribution panel. Category B utilization means it's designed for selectivity with downstream breakers — the 25 ms maximum breaking time lets upstream devices ride through a fault without tripping.

Integration checklist

Mounts on a rail base plate with a 115 mm connection pitch without spreader. The 395 mm depth, 441 mm width, and 439 mm height require a swing-clear door or adequate front access for drawout racking. IP40 protection means it's for indoor panel installation — no washdown exposure. The electronic EVS Trip System2.0 provides LI protection (overload long-time and instantaneous short-circuit) with a 20-minute thermal memory that accounts for prior heating when re-energizing after a trip.

MPN
EVS20H3MW20