Skip to main content
Schneider Electric EVS20H3MW5A

Schneider Electric EVS20H3MW5A EasyPact EVS Circuit Breaker,

MPN EVS20H3MW5A
Active

Schneider Electric EasyPact EVS, EVS20H3MW5A, 3-pole drawout circuit breaker, 2000 A rated current, 65 kA Icu at 440 V AC, electronic trip unit EVS Trip System5A.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

EVS20H3MW5A key specifications
ParameterValue
Control typeManually operated
Display typeDigital display
Trip unit typeElectronic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity65 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Utilization categoryCategory B
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C

All specifications

EVS20H3MW5A additional specifications
ParameterValue
Temp operating max70 °C
Temp operating min-5 °C
Pollution degree4 conforming to IEC 60664-1
Depth395 mm
Width441 mm
Height439 mm
Mechanical life cycles20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
ApplicationDistribution
Operating temperature-5...70 °C

Product details

The Schneider Electric EVS20H3MW5A is a 3-pole drawout air circuit breaker from the EasyPact EVS range, rated 2000 A at 40 °C and built to IEC 60947-2 for distribution duty.

Drawout mounting and panel integration

Drawout mounting means the breaker chassis stays wired to the bus; the moving portion pulls out for inspection or swap without disturbing the main connections. The rear connection position and 115 mm connection pitch without spreader define the bus-bar drill pattern — verify the existing switchgear footprint against the 441 mm width and 439 mm height before committing the cutout. IP40 front face keeps tools and fingers out; pollution degree 4 per IEC 60664-1 confirms it is rated for conductive-dust environments typical of industrial MCC rooms.

Category B utilisation means the breaker is intended for distribution, not direct motor starting — it handles occasional fault clearing, not daily switching of load current. Electrical durability is 5000 cycles at rated voltage without maintenance; mechanical durability is 20000 cycles with maintenance, 10000 without. The suitability-for-isolation mark per IEC 60947-2 and the contact position indicator let you use it as a visible-break disconnect for lockout-tagout — no separate isolator needed.

MPN
EVS20H3MW5A