Skip to main content
Schneider Electric EZ9F34350

Schneider Electric EZ9F34350 Easy9 MCB, 50 A, 3P, C-Curve, 4

MPN EZ9F34350
Active

Schneider Electric Easy9 series, EZ9F34350 miniature circuit breaker, 3P, 50 A, C-curve, 4.5 kA breaking capacity at 400 V AC, clip-on DIN rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

EZ9F34350 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage400 V AC 50/60 Hz
Insulation voltage ui500 V AC 50/60 Hz conforming to IEC 60898-1
Breaking capacity4500 A Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1 4500 A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1
Poles3P
IP ratingIP20
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-25 °C

All specifications

EZ9F34350 additional specifications
ParameterValue
Storage temperature-40...85 °C
Pollution degree2
ColorGrey (RAL 7035)
Depth66.5 mm
Width54 mm
Height81 mm
Electrical life cycles4000 cycles
Mechanical life cycles10000 cycles
ApplicationDistribution
Operating temperature-25...60 °C

Product details

The Schneider Electric EZ9F34350 is a 3-pole miniature circuit breaker from the Easy9 range, rated 50 A with a C-curve trip characteristic. It protects branch circuits in distribution panels against overloads and short circuits, with a breaking capacity of 4.5 kA at both 230 V and 400 V AC per IEC 60898-1. The C-curve means magnetic tripping occurs between 5 and 10 times the rated current (250–500 A), which suits mixed resistive and moderate inductive loads like lighting, small motors, and general-purpose outlets in commercial or residential distribution boards.

Clip-on mounting to DIN rail (35 mm per EN 60715) — the 54 mm width occupies 6 module pitches at 9 mm each, so it fits standard distribution board spacing. Depth is 66.5 mm, height 81 mm. Terminal capacity: 1–35 mm² rigid or 1–25 mm² flexible wire per tunnel terminal, tightened to 3.5 N·m.

The 4.5 kA Icn at 400 V AC is the rated short-circuit breaking capacity — the maximum fault current this MCB can safely interrupt. The service breaking capacity (Ics) is 4.5 kA at 100% of Icn, meaning after one fault at rated capacity the breaker can still be reused. For installations where the prospective short-circuit current exceeds 4.5 kA, a higher-rated device is needed upstream. Rated insulation voltage (Ui) is 500 V AC, and operational voltage (Ue) is 400 V AC — the breaker is suitable for 3-phase 400 V line-to-line distribution networks. Pollution degree 2 and tropicalisation class 2 cover normal indoor environments with some humidity and temperature cycling.

MPN
EZ9F34350