Skip to main content
Schneider Electric EZC100H4075

Schneider Electric EZC100H4075 EasyPact EZC100H 75A 4P MCCB,

MPN EZC100H4075
Active

Schneider Electric EasyPact EZC100H, 4-pole MCCB, 75 A TM-D trip, 30 kA Icu at 400 V AC, thermal-magnetic, front-connected, toggle control.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

EZC100H4075 key specifications
ParameterValue
Control typeToggle
Network typeDC AC
Trip unit typeThermal-magnetic
Main product or component typeCircuit breaker
Voltage550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2
Insulation voltage ui690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 10 kA Icu at 250 V DC 2P conforming to IEC 60947-2 10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 380...400 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2
IP ratingIP20
Terminal pitch25 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C

All specifications

EZC100H4075 additional specifications
ParameterValue
Temp storage min-35 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-35...85 °C
Pollution degree3 conforming to IEC 60947
Depth60 mm
Width100 mm
Height130 mm
Mechanical life cycles13000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

What the 30 kA at 400 V means for your panel

At 220–240 V AC that figure rises to 50 kA Icu, and at 110–130 V AC it reaches 100 kA Icu, all certified to IEC 60947-2. For DC circuits it delivers 10 kA Icu at 125 V DC (1-pole) or 250 V DC (2-pole). That spread covers most distribution panels in light industrial and commercial buildings where the transformer impedance keeps prospective fault current under 30 kA.

Integration — panel fit and connection

The breaker mounts to a backplate (fixed mounting, not DIN rail) with a 25 mm connection pitch. Both line and load connections are front-accessed, so it panels into a standard distribution board without rear-bus adaptors. Dimensions are 100 mm wide × 130 mm high × 60 mm deep — a 4-pole MCCB that fits a 100 mm module slot.

Trip unit and protection — what the TM-D does

Mechanical durability is rated at 13,000 cycles — typical for a distribution MCCB that sees infrequent switching.

MPN
EZC100H4075